Assembling the paneling
▶ Push out the pre-formed slots in the boiler’s side panel [12] or [8]
depending on installed control panel location.
▶ Perforate the membranes of the control panel cable grommets. Route
the electrical cables through them and insert the sensors in their
wells.
▶ Fix the control panel to the boiler casing using the screws provided.
▶ Fit the front side panels [12] and [8] and rear side panels [14] and
[6] over the boiler frame [10] and to the top side beams.
▶ On models 800 to 1550, also fit side panels [13] and [7].
▶ Secure the side panels in place using the top cross beams [19] and
the screws provided.
▶ Fit the top rear panel [17], the bottom rear bracket [15] and then the
bottom rear panels [16] and [18]. Fit the front top panel [5].
▶ Fit the top panels [1], [2], [4] and [3].
▶ Finally, fit the front trim panels [11] and [9].
SB625WS
SB745WS
160
220
290
370
480
640
800
1050
1300
1550
Recommended Service
A1
inch
(mm)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
A2
inch
(mm)
64,00
(1626)
64,00
(1626)
65,00
(1630)
73,00
(1830)
81,00
(2035)
88,00
(2235)
101.00
(2560)
111.00
(2810)
119.00
(3010)
122.00
(3080)
B1
inch
(mm)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
B2
inch
(mm)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
D
inch
(mm)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
36,00
(915)
Minimum Service
A1
inch
(mm)
24,00
(610)
24,00
(610)
24,00
(610)
24,00
(610)
24,00
(610)
24,00
(610)
24,00
(610)
24,00
(610)
24,00
(610)
24,00
(610)
A2
inch
(mm)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
B1
inch
(mm)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
B2
inch
(mm)
C+4
(C+100)
C+4
(C+100)
C+4
(C+100)
C+4
(C+100)
C+4
(C+100)
C+4
(C+100)
C+4
(C+100)
C+4
(C+100)
C+4
(C+100)
C+4
(C+100)
D
inch
(mm)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
Clearance to combustibles
A1
inch
(mm)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
A2
inch
(mm)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
64,00
(1626)
B1
inch
(mm)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
B2
inch
(mm)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
6,00
(152)
D
inch
(mm)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
18,00
(457)
Table 8 Boiler clearances
Smaller models (160/220/290) have only two top
panels, one over the right and one over the left of the
boiler.
Control panel may be fitted on either side or top panel of
boiler.
Summary of Contents for Buderus SB625WS
Page 51: ... 51 6 720 805 218 2013 02 SB625WS SB745WS Notes ...
Page 52: ......