23
Installation Instructions
Bosch Climate 5000 Series Wall Mounted Ductless Split Air Conditioner / Heat Pump (06.2022)
4.
Remove tape from ends of pipe when ready to perform fl aring work.
5.
Clamp fl are form on the end of the pipe. The end of the pipe must extend
beyond the edge of the fl are form in accordance with the dimensions shown
in the Table 6.
Figure 29
Piping extension beyond
fl
are form
Outer diameter
of tube mm (in.)
A mm (in.)
Min.
Max.
Ø 6.35 (Ø 0.25”)
0.7 (0.0275”)
1.3 (0.05”)
Ø 9.52 ( Ø 0.375”)
1.0 (0.04”)
1.6 (0.063”)
Ø 12.7 ( Ø 0.5”)
1.0 (0.04”)
1.8 (0.07”)
Ø 16 ( Ø 0.63”)
2.0 (0.078”)
2.2 (0.086”)
Table 6
Figure 30
Flaring tool
Tube
A
6.
Place fl aring tool onto the fl aring block.
7.
Turn the handle of the fl aring tool clockwise until the pipe is fully fl ared.
8.
Remove the fl aring tool and fl aring block, then inspect the end of the pipe
for cracks and even fl aring. Slide the nut up to see if the fl are is of proper
diameter and does not interfere with the threads in the fl are nut.
Step 4: Connect refrigerant line set
When connecting refrigerant pipes, be careful not to use excessive torque or to
deform the piping in any way. You should fi rst connect the low-pressure (suction)
pipe, then the high-pressure pipe (liquid line).
Minimum Bend Radius
When bending connective refrigerant piping, the minimum bending
radius is 10cm (4in). See Figure 32.
Figure 31
≥10cm (4in)
Radius