Installation Instructions
Bosch Climate 5000 Series Wall Mounted Ductless Split Air Conditioner / Heat Pump (06.2022)
Mounting plate dimensions
Diff erent models have diff erent mounting plates. In order to ensure that you have
ample room to mount the indoor unit, the diagrams to the right show diff erent types
of mounting plates along with the following dimensions:
Width of mounting plate
Height of mounting plate
Width of indoor unit relative to plate
Height of indoor unit relative to plate
Recommended position of wall hole (both to the left and right of mounting
plate)
Relative distances between screw holes
Correct orientation of Mounting Plate
Make sure the mounting plate is level and not leaning to one side.
Figure 4
Mounting plate differences
Figure 5
6k, 9k & 12k Btuh Models
Indoor unit outline
795(31)
120(4.7)
Φ
pipe hole
65(2.5)
50(1.9)
Φ
pipe hole
65(2.5)
425(16.7)
295(11.6)
51(2.0)
40(1.6)
Figure 6
18k Btuh Model
Φ
FROM EDGE T
O
HOLE CENTER:50mm
FROM EDGE T
O
HOLE CENTER:95mm
150
100
100
965(38)
50(1.9)
95(3.7)
pipe hole
65(2.5)
Φ
pipe hole
65(2.5)
490(19.3)
322(12.7)
40(1.6)
40(1.5)
100
50
50
50
2
2
2
4
4
4
6
RECOMMAND
LIQUID
GAS
BUBBLE
LEVEL
mm
inch
mm
inch
Indoor unit outline
Figure 7
24k, 30k & 36k Btuh Models
FROM EDGE T
O
HOLE CENTER:50mm
FROM EDGE T
O
HOLE CENTER:70mm
570.7(22.5)
70(2.8)
1140(44.8)
50(1.9)
Φ
pipe hole
65(2.5)
Φ
pipe hole
65(2.5)
370(14.6)
50(1.9)
60(2.4)
BUBBLE
LEVEL
150
100
50
2
4
6
RECOMMAND
mm
inch
100
100
50
50
2
2
4
4
LIQUID
GAS
mm
inch
Indoor unit outline
When the gas side connective pipe is ⌀16mm(5/8in) or more, the wall
hole should be 90mm(3.54in).
Step 3: Drill wall hole for connection
You must drill a hole in the wall for refrigerant piping, the drainage pipe, and the
signal/power cable that will connect the indoor and outdoor units.
1.
Determine the location of the wall hole based on the position of the mounting
plate. Refer to Mounting Plate Dimensions on the next page to help you
determine the optimal position. The wall hole should have a 65mm (2.5in)
diameter at least, and at a slightly lower angle to facilitate drainage.
2.
Using a 65mm (2.5in) core drill, drill a hole in the wall. Make sure that the
hole is drilled at a slight downward angle, so that the outdoor end of the hole
is lower than the indoor end by about 5mm to 7mm (0.2-0.275in). This will
ensure proper water drainage. (See Fig. 4)
3.
Place a protective wall sleeve (not included) in the hole. This protects the
edges of the hole and will help seal it when you fi nish the installation process.
CAUTION: ELECTRICAL SHOCK/PROPERTY DAMAGE
When drilling the wall hole, make sure to avoid wires,
plumbing, and other sensitive components.
Figure 8
Wall
Indoor
Outdoor
m
m
7-
5
(0.2
-0.3in)