Service Manual
Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Multi Zone Outdoor Units
| 53
Bosch Thermotechnology Corp.
|
08.2020
Data subject to change
DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3,
pin3-pin4 in fan motor connector. If the value of the voltage is not in the range
showing in below table, the PCB must have problems and need to be replaced.
Figure 60
Figure 61
Vs
Vcc
Vsp
FG
DC motor voltage input and output
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
200~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
13.5~16.5V
5
Yellow
Vsp
0~6.5V
6
Blue
FG
13.5~16.5V
Table 26