en | Adjustment of detection settings
AVIOTEC IP starlight 8000
2020.08 | 01 | F.01U.391.015
Operation and Commissioning Manual
Bosch Sicherheitssysteme GmbH
Verification time [s]
of the smoke detection can be set from 10 to 30 seconds. The default
value is 15 seconds. Small values cause faster detection (higher risk of false alarms), larger
values decrease false alarms.
Sensitivity
In case of false alarms, you can use a software slider to adapt the value
Sensitivity
for flame
and smoke to your specific needs. The following table shows the different settings:
Sensitivity
low
mid
high
Smoke
–
High contrast
and colored
objects in the
video image
cause false
alarms.
(recommendatio
n: set also
Verification
time [s]
to 20s)
–
Slow moving
objects (e.g.
cranes, slow
vehicles,
automatic
doors) cause
false alarms.
(recommendatio
n: set also
Verification
time [s]
to 20s)
Default setting
If no moving objects
are expected.
Flames
Blinking lights or
fans cause false
alarms.
(recommendation:
set also
Verification
time [s]
to 12s)
Default setting
If no moving objects
and no blinking lights
are expected.
7.2
Adjustments of image regions
Notice!
There is no fire detection in privacy defined masks created in the Intelligent Video Analytics.