OMD10078 rev F
49
5.2.12 Technical data
Picture 36 – Technical data of battery isolator
-
Colour:
RAL
7035
-
Protection
degree:
IP20
UPS (kVA)
60 80 100
125
160
L – mm
500
P – mm
250
H – mm
700
L1 – mm
460
H1 – mm
660
UPS (kVA)
60
80
100
125
160
Isolator type
4-pole Is Fuses
Fuse size (A)
200 gG 200 Gg 200 Gg 250 Gg 315 Gg