OMD10078 rev F
25
4.4
POSITIONING AND INSTALLATION
The UPS B9000FXS must be installed indoor, in a clean and dry room, preferably
without dust or humidity infiltrations.
Special environmental conditions
It is necessary to implement specific protective measures in case of unusual
environmental conditions:
harmful smoke, dust, abrasive dust;
humidity, vapour, salt air, bad weather or dripping;
explosive dust and gas mixture;
extreme temperature variations;
bad ventilation;
conductive or radiant heat from other sources;
fungus, insects, vermin.
4.4.1 Base plan, static load and weights
Picture 21 – Base plan
UPS (kVA)
60 80 100
125
160
L1 – mm
815
P1 – mm
825
L2 – mm
70
The supporting base of the UPS must be designed to carry the UPS weight and to
ensure its steady and safe support.
Its carrying capacity must be adequate to the static loads indicated in the table
below.
UPS (kVA)
60 80 100
125
160
Weight - kg
570
600
630
662
720
Static load – kg/m
2
948 998 1048
1101
1198