11
3) Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
C-45
C
<95%
<1000m
-15
C-50
C
Note: if the UPS is installed or used in a place where the altitude is
above than
1000m
, the output power must be derated in use, please
refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Maximum
Power
100% 95% 91% 86% 82% 78% 74% 70% 67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Current
crest ratio
1%
0.9 lag
Synchronized
50/60Hz
10% in
Line mode (AC
mode)
0.1% of normal
frequency in Battery
mode
THD<2% Full
load (Linear
Load)/
≤
5% for
reference
non-linear load
100%-110% load
transfers to Bypass
mode after 5 minutes
110%-130% load
transfers to Bypass
mode after 1 minutes
130%-150% load
transfers to Bypass
mode after 10 second
≥
150% load transfers to
Bypass mode after 2
second
3:1