36
Fig. 5.12
Fig. 5.13
Battery fail:
If the battery status detected is “bad battery
detected” or “battery disconnected”, the
symbol of battery failure will be shown and
the UPS will alarm.
5.3 Turning on and Turning off UPS
Attention:
The UPS should only be turned on while connecting with the
utility for the first time.
Attention:
Connected loads should be switched off before turning on
the UPS.Loads may yhen be added one at a time after the UPS is turned
on. Switch off all connected loads before turning off the UPS.
5.3.1 Turning on UPS with utility
1) Check all the connections are correct.
2) Power on the UPS, the fan begins to work. LCD shows the
“Welcome” logo. The LCD will then show the default UPS
status summary screen.
3) Press and hold
button continuously for more than 1 second.
The buzzer will beep for 1s and the UPS turns on.
4) A few seconds later, the UPS goes to Line mode. If the utility
power is abnormal, the UPS will transfer to Battery mode
without output interruption of the UPS.