Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
OMD10013 REV. I
35
8
BYPASS START UP
WAIT PLEASE
The control logic checks that all the bypass
parameters (voltage, phase rotation,
frequency) are correct. LED #2 is lit green:
bypass voltage present
9 BATTERY
START
UP
CLOSE BCB
Close BCB
10 BATTERY
START
UP
WAIT PLEASE
The control logic checks the closing of the
circuit breaker to go to the following step.
Led #4 lit green.
11
UPS START UP
CLOSE OCB
Close OCB
12
START UP END
WAIT PLEASE
The control logic checks that all the output
parameters (voltage, current, frequency) are
correct. LED #7 is lit green: output voltage
present.
End UPS
MODEL
OUTPUT VOLTAGE
The default screen is displayed after a short
time with the UPS model and the values of
output voltage.
5.3
BASIC TROUBLESHOOTING
This paragraph provides the basic information if any problems occur during the start-up
procedure. In case the problem cannot be solved, contact the service department.
1) After closing RCB the LCD display is still blank
Check the phase rotation of supply voltage.
Make sure the input voltage and frequency are within tolerance.
Check the rectifier protection fuses F1-F2-F3; they are inside the unit.
2) After step #1 the UPS stops the starting sequence and shows one or more alarm
messages
Check the alarms indicated on the display and remove their causes.
Close RCB and try to restart the UPS.
3) After step #2 the unit shows the alarm A15 – Byp fault
Make sure you have closed circuit breaker SBCB.
Check the protection fuses of the static bypass switch; they are inside the unit.
Check the phase rotation of the bypass voltage.
Make sure voltage and frequency are within tolerance.
4) After step #3 the unit shows the alarm A7 – BCB open
Make sure you have closed the battery circuit breaker; the circuit breaker or the
fuse carrier is external to the UPS system.
Check the battery fuses.
Check the interconnection between the auxiliary contact of the battery circuit
breaker (in the external cabinet) and the terminals Bac1-Bac2 of the UPS.
Summary of Contents for ASD10
Page 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B9000FXS 60 80 100 125 160kVA ...
Page 2: ......
Page 5: ...Warnings and general information Avvertenze e informazioni generali 2 OMD10080 REV B ...
Page 96: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 5 ENGLISH LANGUAGE ...
Page 142: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 51 LINGUA ITALIANA ...