Borg & Overström
GB
16
Install & Operation Manual
1. Switch on Mains power – the display will
flash several times, then the fridge system
will switch on and the display will give a
steady reading, this is the temperature of
the water bath sensor.
2.
Press and release the ‘Set’ button – The
display will show ‘SET’.
3.
Press ‘Set’ again and the display will show
a numeric value (e.g. 9°C).
4.
Raise or lower this figure to the desired
setting using the up or down arrows on the
left of the control display window.
5. When the correct setting is shown in the
display window press ‘Set’ button the
display will now show SET.
6. Press FNC button to return to the probe
temperature reading.
Basic Settings
8888
8888
Adjusting the Set Point:
1.
Press and hold the ‘Set’ button until CP
shows on the display – Release the button.
2. Press ‘Set again, DIF will show on the
display.
3.
Press ‘Set’ again and the display will show
a numeric value, (e.g. 1°C, the default
setting.)
4.
Raise or lower this figure to the desired
setting using the up or down arrows on the
left of the control display window.
5. When the adjustment has been made
press ‘Set’ again the display will show DIF.
6. If no further changes are required press
FNC again to exit.
Altering the Differential setting:
8888
8888
8888
NOTE:
If no buttons are pressed for 15 seconds, the control will revert to temperature display mode,and any
changes to settings will be saved.
Controls
Power Connection Socket
Note:
the undercounter unit
automatically powers up when the
power lead is connected.
8888
Control Button
Eliwell Control Panel
Control Button
Function Button
Setting Button
Digital Display