47
Installation and Maintenance
Service Manual
(4) Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8
Main detection points:
● Instant energization afte de-energization while the capacitordischarges slowly?
● ����������������������������������
Malfunction diagnosis process:
Turn power off for
1minute,the turn
back on
The unit returns to normal.
Conclusion:U8 is displayed due to
power off/on while the
capacitor discharges slowly.
U8 is still
displayed
The zero-cross detection circuit
��������������
abnormal.Replace the mainboard
with the same model
Yes
No
Start
End
Summary of Contents for Brisa BRS09HPL1IA/OA
Page 20: ...17 Technical Information 6 Function and Control 6 1 Remote Controller Introduction...
Page 21: ...18 Service Manual...
Page 22: ...19 Technical Information...
Page 23: ...20 Service Manual...
Page 24: ...21 Technical Information...