7
3. TECHNICAL SPECIFICATIONS - CAPACITY AND CONSUMPTION
Table 1
Technical Specifications of steam generator UNI-MATIC UM.*
UNIMATIC – TECHNICAL DATASHEET
Features
Unit
UM 30
UM 50
UM 100
UM 150
UM 200
UM 300
Steam production
Kg/h
300
500
1.000
1.500
2.000
3.000
Design pressure
bar
11,7
11,7
11,7
11,7
11,7
11,0
Max working pressure
bar
10.0
10.0
10.0
10.0
10.0
9.0
TOTAL ELECTRIC POWER
Heavy fuel oil
KW
4,3
5,3
9,6
12,9
16,0
24,0
Natural gas or diesel oil
KW
2,3
2,3
4,6
5,9
7,0
12,0
FUEL CONSUMPTION AT 100% OF THE LOAD
Heavy fuel oil
Kg/h
21,1
35,1
70,3
105,4
140,6
210,9
Natural gas
Nm
3
/h
24,1
40,1
80,2
120,3
160,4
240,6
Diesel oil
kg/h
20,1
33,4
66,8
100,3
133,7
200,5
FUEL CALORIFIC POWER
Heavy fuel oil
Kcal/kg
9.700
8.500
10.200
Natural gas
Kcal/Nm
3
Diesel oil
Kcal/kg
Standard electric
power data
380 V / 50 Hz / 3 phases with neutral
Auxiliaries voltage
220 V
Feeding and boiler
water norm
EN 12952 – 12:2003 (up to European standard)
* -
These are generalized technical information for all UNI-MATIC range model.
Please ask for specific measures indications and eventual available modifications.