BONNET CIDELCEM GRANDE CUISINE
Siége social:
Rue des Frères Lumière - Z.I Mitry Compans
77292 MITRY MORY Cedex
D
ESIGNATION
230 V a.c.
230 V 3 a.c.
400 V 3N a.c.
Radiant hobs on neutral cupboard in 500
-
4 x 6 mm
2
5 x 2.5 mm
2
Radiant hobs on heated cupboard in 500
-
4 x 6 mm
2
5 x 2.5 mm
2
Radiant hobs on neutral cupboard in 1000
-
4 x 6 mm
2
5 x 6 mm
2
Radiant hobs on heated cupboard in 1000
-
-
5 x 6 mm
2
Radiant hobs on electric oven in 1000
-
-
5 x 6 mm
2
Solid top on neutral cupboard in 500
-
4 x 6 mm
2
5 x 2.5 mm
2
Solid top on heated cupboard in 500
-
4 x 6 mm
2
5 x 2.5 mm
2
Solid top on neutral cupboard in 1000
-
4 x 6 mm
2
5 x 2.5 mm
2
Solid top on heated cupboard in 1000
-
-
5 x 6 mm
2
Solid top on electric oven in 1000
-
-
5 x 6 mm
2
Plancha on neutral cupboard in 500
-
4 x 2.5 mm
2
5 x 2.5 mm
2
Plancha on heated cupboard in 500
-
4 x 4 mm
2
5 x 2.5 mm
2
Plancha on neutral cupboard in 1000
-
4 x 6 mm
2
5 x 2.5 mm
2
Plancha on heated cupboard in 1000
-
4 x 6 mm
2
5 x 4 mm
2
Induction 6 + 3 on cupboard in 500
-
-
5 x 2.5 mm
2
Bar grill on neutral cupboard in 500
-
4 x 4 mm
2
5 x 2.5 mm
2
Bar grill on neutral cupboard in 1000
-
4 x 6 mm
2
5 x 4 mm
2
Bain marie on neutral cupboard in 500
3 x 2.5 mm
2
4 x 2.5 mm
2
5 x 2.5 mm
2
Bain marie on heated cupboard in 500
3 x 2.5 mm
2
4 x 2.5 mm
2
5 x 2.5 mm
2
Bain marie on neutral cupboard in 1000
3 x 2.5 mm
2
4 x 2.5 mm
2
5 x 2.5 mm
2
Bain marie on heated cupboard in 1000
3 x 4 mm
2
4 x 4 mm
2
5 x 4 mm
2
French fry store on heated cupboard in 500
3 x 2.5 mm
2
-
-
French fry store Infra red on neutral cupboard in 500
3 x 2.5 mm
2
-
-
French fry store Infra red on heat cupboard in 500
3 x 2.5 mm
2
-
-
Neutral top on heated cupboard in 500
3 x 2.5 mm
2
-
-
Neutral top on heated cupboard in 1000
3 x 2.5 mm
2
-
-
Provide a suitable isolating device (with contact separation of at least 3mm) in accordance with current
regulations.
The installation must comply with current applicable national legislation (for France, standard NF
15.100).
The appliance must be connected to the earth. The various electrical appliances must also be
connected with an equipotential contact (earth continuity bonding) to the equipotential terminal located
next to the connection cable gland.
The manufacturer cannot be held responsible in the event that these instructions are not
respected.