background image

26

 

 

Appendix D 

(For reference) 

Example of Arranging Equipment on the Door of 

ShPS-12, ShPS-12 mod.02, ShPS-12 mod.10, or ShPS-12 mod.12 

using MK-1 ShPS Mounting Kit 

 

S2000-4

6

7

8

9

10

SIGNAL-10

S2000-KDL

RS-485

LOOP

S2000-KPB

COM

MASS

PRES

READY

READY

READY

READY

 

Summary of Contents for ShPS-12

Page 1: ...SрPS 12 FIRE EQUIPMENT MOUNT BOXES WITH BACKUP BATTERY POWER SUPPLIES ShPS 12 ShPS 12 mod 01 ShPS 12 mod 02 ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 User s Manual ...

Page 2: ... 13 2 2 4 Wiring the ShPS 12 14 2 2 5 Programming the ShPS 12 15 2 2 6 Usage 16 2 2 7 Performance Testing 17 2 2 8 Extreme Situation Actions 19 2 2 9 Troubleshooting 19 3 Maintenance 19 3 1 General 19 3 2 Safety Precautions 19 3 3 Maintenance Procedures 20 3 4 Operability Testing 20 3 5 Technical Examination 20 3 6 Preservation Depreservation Represervation 20 4 Repair 20 5 Storage 20 6 Transporti...

Page 3: ... Signal 10 Signal 20P S2000 4 S2000 KDL S2000 KPB S2000 SP1 S2000 PI S2000 KDL 2I Rupor mod 02 S2000 PGE S2000 PGE mod 01 S2000 Ethernet S2000 RPI and other devices mountable on a 35 mm top hat DIN rail in accordance with GOST R MEK 60715 2003 1 1 3 ShPS 12 mod 10 ShPS 12 mod 11 and ShPS 12 mod 12 are intended for operation with Sirius Fire Alarm Control Panel and C2000M Monitoring and Control Pan...

Page 4: ... or similar 12 V 17 Ah 2 batteries 1 2 4 Output voltage while powered by mains 13 6 0 6 V batteries 13 5 9 5 V 1 2 5 Rated maximum load current 3 A 3 5 A 1 2 6 Outputs for powering devices consuming 12 V and installed within ShPS 12 7 1 2 7 Maximum current per a single output 12V dc 0 65 A 1 2 8 Outputs for connecting RS 485 interface lines installed within ShPS 12 7 1 2 9 For ShPS 12 ShPS 12 mod ...

Page 5: ...5 interface messages about presence of relevant voltages faults battery dis charge bad battery health and battery disablement and tampering 1 2 33 The built in PSU of ShSP 12 is ready to operate after 6 seconds upon powering up 1 2 34 A ShPS 12 features a Remote Fault Output a solid state relay with the following parameters maximum switched voltage current is 80 V 50 mA maximum resistance of close...

Page 6: ...ons Manual 1 Note No battery is included in the standard delivery 1 4 Arrangement and Operation 1 4 1 A ShPS 12 is assembled within a metal enclosure The enclosure consists of a cabinet and a key lockable door On the outer surface of the door there are light indicators to indicate the ShPS 12 conditions The cabinet houses the MIP 12 power supply module the BK 12 switch unit for connections and cir...

Page 7: ... process does not start If for the ShPS 12 box no measurement of battery capacity was carried out during operation and the ShPS 12 box is requested for backup operation time and time to measure the capacity it will calculate these details on the assumption of installed batteries of 17 Ah capacities and the output current value f If an unacceptable output overload or short circuit fault occurs the ...

Page 8: ...and current values to charge the batteries Power Failed the mains power being applied to the box the ShPS 12 does not provide functions according to 1 2 4 Power Restored the mains power being applied to the box the ShPS 12 provides functions according to 1 2 4 Battery Fault voltage of any of the batteries is lower than 7V or batteries are not connected Battery Test Error battery internal resistanc...

Page 9: ...PUT ADC Select the Input ADC item using the 43 buttons and click or click 2 for quick navigation ADDRESS _ Enter the device address 1 to 127 or select it from the menu using the 43buttons and press INPUT _ Enter the required input number or select it from the menu using the 4 3buttons and press The requested data are presented in the form of text and specific ADC values Input Information on the S2...

Page 10: ... adjusted in the appeared dialog box The ShPS 12 will adjust the selected values to the values of mains voltmeter after saving configuration and reset 1 4 3 Operation of ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 under Sirius Panel To request conditions as well as to view various values measured by the ShPS 12 by means of the Sirius Fire Alarm Control Panel do the following as stated in the Siri...

Page 11: ...lity Firmware Update The last version of this program is available online at the address of http bolid ru To switch the BK 12 RS485 to the programming mode please close the jumper circuit ХР5 PROG on the board of the BK 12 RS485 The programming mode is indicated by two board LEDs blinking once per second Only one of the separate RS 485 interfaces is used for updating 1 5 Measuring Instruments Tool...

Page 12: ...be carried out until the equipment mount box is disconnected from the mains power Installation and maintenance shall be carried out by professionals qualified for Accident Prevention of Class III or higher 2 2 3 1 Mounting Equipment Inside Box The Box is used to house and power housed Orion ISS equipment or other devices meant for the DIN rail installation The Appendices B and C show options of ho...

Page 13: ...all be connected to ХТ1 1 2 see Appendix A e Mount batteries and connect them to terminals observing the polarity the red wire shall be connected to the lead of the battery while the blue wire shall be connected to the lead of the battery Connect О shape terminal of thermal sensor to the battery lead as shown in Figure 1 according to Appendix A f Turn on the QF1 and QF2 circuit breakers Note Rated...

Page 14: ...longer than 1sec Reset network address to set default address 127 Reset battery life counter and measured capacity when battery replaced 2 2 5 4 If the network controller is powered from another power supply the circuits 0 V of the ShPS 12 ShPS 12 mod 01 ShPS 12 mod 02 box and network controller shall be connected as a single circuit 2 2 5 5 The programmable parameters are described in Table 5 and...

Page 15: ...run ning right after powering on the ShPS 12 or reboot Turn On Turn Off Turn On for a Time Turn Off for a Time Turn Off 2 Relay Activa tion Time Time for the relay to be turned on off for the com mands Turn On for a Time and Turn Off for a Time 0 8191 875 s 8191 875 s 3 Relay Control Option Selection of monitored pa rameters to activate the relay control program 1 All parameters but for communi ca...

Page 16: ...acity Measurement To make the capacity measurement available the battery charge level shall be more than 80 Note The battery charge volume being less than 80 the ShPS 12 cannot measure the capacity of installed batteries a To measure the ShPS 12 battery capacity using the S2000M panel please use the Test Detector function see S2000M Users Guide When initiating a testing command please specify 0 fo...

Page 17: ... ShPS 12 load 2 Time Limited The test is to be completed at the end of the time period given in the field below This test option is recommended if you want to get info on the ShPS 12 functionality in the backup mode for the time specified If batteries are discharged lower than 80 during the Time Limited test the ShPS 12 can calculate the actual capacity of the batteries installed in the ShPS 12 bo...

Page 18: ...cantly reduced bat tery capacity 2 Battery leads oxidation or loosened battery contacts 1 Replace batteries 2 Clean leads tighten wire connections of the battery ShPS 12 issues the Ser vice Required message Battery lifetime expired Replace the batteries and reset the lifetime counter Lost communications between the ShPS 12 and network controller 1 Failed connection between the ShPS 12 and controll...

Page 19: ... rules of mounting and operation is not a reason for claims and warranty repair Claims should be submitted to the following address NVP BOLID 4 Pionerskaya Str Korolyov Moscow Region 141070 Russia Phone fax 7 495 775 71 55 PBX E mail info bolid ru In case of any issue related to use of the product please contact the technical support 7 495 775 71 55 or e mail support bolid ru 5 Storage Storage in ...

Page 20: ... the manufacturer s date of production 9 Certification Information 9 1 ShPS 12 ShPS 12 mod 01 ShPS 12 mod 02 ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 meet the requirements of Technical Regulations of Custom Union TR CU 004 2011 TR CU 020 2011 and are covered by Conformity Declaration ЕАЭС RU Д RU НА74 В 00197 19 9 2 ShPS 12 ShPS 12 mod 01 ShPS 12 mod 02 ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mo...

Page 21: ...5 A1 14 B1 13 0 12 U 11 A2 10 B2 9 0 8 U 7 A3 6 B3 5 0 4 U 3 A4 2 B4 1 B A 17 18 ХТ2 Neutral Line ХТ1 3 ХТ1 2 ХТ1 1 ХТ3 3 ХТ3 2 N L Neutral Earthling Blue Red Fault relay output 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 17 18 0 V V 0 U A6 B6 0 U A5 B5 A8 B8 0 U A7 B7 Line Blue Red 1 8 ...

Page 22: ...23 Schematic for Wiring ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 ...

Page 23: ...24 Appendix B For reference Example No 1 of fitting together equipment within ShPS 12 ...

Page 24: ...25 Appendix C For reference Example No 2 of fitting together equipment within ShPS 12 ...

Page 25: ...Example of Arranging Equipment on the Door of ShPS 12 ShPS 12 mod 02 ShPS 12 mod 10 or ShPS 12 mod 12 using MK 1 ShPS Mounting Kit S2000 4 6 7 8 9 10 SIGNAL 10 S2000 KDL RS 485 LOOP S2000 KPB COM MASS PRES READY READY READY READY ...

Page 26: ...27 Appendix E Overall and Mounting Dimensions For ShPS 12 ShPS 12 mod 02 ShPS 12 mod 10 ShPS 12 mod 12 320 103 320 140 Шпильки для установки реек DIN Rail Pins ...

Page 27: ...28 Appendix F Overall and Mounting Dimensions For ShPS 12 mod 01 and ShPS 12 mod 11 ...

Page 28: ...29 Appendix G For reference Window Sizes and Position on the Door ShPS 12 mod 01 and ShPS 12 mod 11 ...

Page 29: ...30 Appendix H For information UProg Window for Programming ShPS 12 ...

Reviews: