11
Input
Information on the S2000M display
Use the
⊳
buttons to browse measurements
# 3
−
U
акк
= 9,5…14,2V
or
U
акк
= 00,00V
(Battery 1 is not connected to the MIP)
−
Трезерв
= 03
ч
50
мин
(Depends on the battery capacity, output current, and battery temperature)
or
Изм
.
ждите
…
(The MIP-12 is calculating the value, please wait for about a minute)
or
АКБ
ОТКЛЮЧЕН
(No batteries are connected to the MIP)
−
Ттеста
= 03
ч
00
мин
(Depends on the battery capacity, output current, and battery temperature)
or
Заряд
АКБ
<80%
(Battery charge is less than 80%; no capacity can be measured)
or
Изм
.
ждите
…
(The MIP-12 is calculating the value, please wait for about a minute)
or
АКБ
ОТКЛЮЧЕН
(No batteries are connected to the MIP)
−
Ёмкость
17,00
Ач
(The last measured capacity)
or
Ёмкость
не
изм
.
(No battery capacity was measured)
or
АКБ
ОТКЛЮЧЕН
(No batteries are connected to the MIP)
−
Тнар
_
ост
= 43800
ч
(5 years)
# 4
−
U
акк
= 9,5…14,2V
or
U
акк
= 00,00V
(No second battery is connected to the MIP)
# 5
−
Заряд
АБ
100 %
(Charger in norm)
or
Авария
ЗУ
(Charger failed)
or
ЗУ
НОРМА
(No batteries are connected to the MIP; the charger operates properly)
# 6
−
U
сети
= 150…255 V
Note
: * The mains voltage measured by the ShPS-12 can differ if compared to values measured
with a RMS voltmeter. This may be due to distortion of mains power y-voltage, etc. The ShPS-12 can
adjust the main voltage measurements with a 1V increment (in ±20V range). To adjust the
measurements, please run the UProg utility, select the MIP-12-3A RS with the corresponding network
address, and select the values to be adjusted in the appeared dialog box. The ShPS-12 will adjust the
selected values to the values of mains voltmeter after saving configuration and reset.
1.4.3
Operation of ShPS-12 mod.10, ShPS-12 mod.11, ShPS-12 mod.12 under Sirius Panel
To request conditions as well as to view various values measured by the ShPS-12 by means of the
Sirius Fire Alarm Control Panel, do the following (as stated in the Sirius ver.1.00 user’s manual):
a)
Connect the ShPS-12 to the LINE1 and / or LINE2 terminals of the separate RS-485 (UNITS)
interface of the Sirius panel (refer to 7.2.5 of Sirius User’s Guide).
b)
Define the Sirius database through the Configuration tab of the web interface:
−
Add the device MIP-12 into the Sirius database and include it to any zone; give a name for the
device if necessary;
−
Add inputs No.1…No.6 to the Sirius database with input types set to Auxiliary (by default); all
the inputs shall be added to the same zone where the MIP-12 is included. Edit the input names
if necessary;
c)
Authorize your access to the Sirius panel by entering the User PIN 77777.
d)
Press the ZONE button to enter the mode of displaying of all zones and zone groups of the
system.
e)
Using arrow buttons, select the zone the MIP-12 with all its inputs is included into, and then
press Enter to view the zone content.
f)
Using arrow buttons, select the MIP-12 input (or the device itself) which status and measured
values are required to be requested and press Enter to view the received data.
g)
In the Input Information mode, with arrow buttons you can switch between windows of
indicating information on configuration parameters of the input, input multistate (along with event
origin times), and measured ADC values on the input:
Summary of Contents for ShPS-12
Page 22: ...23 Schematic for Wiring ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 ...
Page 23: ...24 Appendix B For reference Example No 1 of fitting together equipment within ShPS 12 ...
Page 24: ...25 Appendix C For reference Example No 2 of fitting together equipment within ShPS 12 ...
Page 27: ...28 Appendix F Overall and Mounting Dimensions For ShPS 12 mod 01 and ShPS 12 mod 11 ...
Page 29: ...30 Appendix H For information UProg Window for Programming ShPS 12 ...