15
as specified in 1.2.17. The batteries shall be fully charged before the test (indicated by steady light of
the BATTERY LED).
2.2.5
Programming the ShPS-12
2.2.5.1.
Change the network address of the ShPS-12 box. The new address shall be unique and
different from all the addresses of devices connected to the same RS-485 line where this ShPS-12 is
connected (default address is 127).
2.2.5.2.
If needed, change the rest configuration parameters according to your intended use of the
ShPS-12 (see Table 5).
To change the ShPS-12 configuration parameters, please use an IBM-compatible computer with the
UProg
application installed. To connect the ShPS-12 to a PC COM port, an interface converter shall
be used such as RS-232/RS-485 PI-GR, S2000-PI, or S2000M panel set as interface converter.
Appendix H shows the application window.
The
UProg
utility can be downloaded at
http://bolid.ru
.
2.2.5.3.
The ShPS-12 door being open, the tamper switch can be used to:
−
Mute the buzzer
by three short and one long tamper button presses (
●
●
●
▬
);
Note: Holding button down for 1.5 to 3 sec is long pressing (
▬
). Holding the button down for 0.1 to
0.5 sec is short pressing (
●
). Pauses between presses shall not be shorter than 0.1 sec but no longer
than 1sec.
−
Reset network address
(to set default address 127): (
▬ ▬ ▬ ●);
−
Reset battery life counter and measured capacity
(when battery replaced): (
●
●
●
▬
▬
).
2.2.5.4.
If the network controller is powered from another power supply, the circuits “0 V” of the
ShPS-12 / ShPS-12 mod.01 / ShPS-12 mod.02 box and network controller shall be connected as a
single circuit.
2.2.5.5.
The programmable parameters are described in Table 5 and Table 6 (see Appendix H). The
parameters are stored in the nonvolatile memory.
2.2.5.6.
Unless the ShPS-12 / ShPS-12 mod.01 / ShPS-12 mod.02 box is the first or the last device
in the RS-485 interface bus then open the XP1 jumper located on the BK-12 board close to the
ХТ
1
terminal block (which is intended for connecting the devices) – see Appendix A.
2.2.5.7.
If the ShPS-12 mod.10 / ShPS-12 mod.11 / ShPS-12 mod.12 box is the first or the last
device in the RS-485 interface bus then loosen the side limiter for connecting the end-of-line resistors
and remove the cover from the BK-12 enclosure. On the BK-12 board, near the terminal block for
connecting the separate RS-485 interface No.2 please find mail-type connectors
ХР
10 and
ХР
11.
Closing the connector
ХР
10 with the jumper provided connects the end-of-line resistor to the separate
RS-485 interface line No.1. Closing the connector
ХР
11 with the jumper provided connects the end-of-
line resistor to the separate RS-485 interface line No.2.
Figure 2
Summary of Contents for ShPS-12
Page 22: ...23 Schematic for Wiring ShPS 12 mod 10 ShPS 12 mod 11 ShPS 12 mod 12 ...
Page 23: ...24 Appendix B For reference Example No 1 of fitting together equipment within ShPS 12 ...
Page 24: ...25 Appendix C For reference Example No 2 of fitting together equipment within ShPS 12 ...
Page 27: ...28 Appendix F Overall and Mounting Dimensions For ShPS 12 mod 01 and ShPS 12 mod 11 ...
Page 29: ...30 Appendix H For information UProg Window for Programming ShPS 12 ...