2

1.2 11.

 

The unit remains functional under and after exposure to electromagnetic interference of the 

third  severity  level  and  higher  in  accordance  with  Russian  Standards

 

ГОСТ

 

Р

 51317.4.2, 

ГОСТ

 

Р

 51317.4.3.  The  quality  of  operation  of  the  unit  is  not  guaranteed  if  electromagnetic 

environment doesn't meet the operation conditions. 

1.2 12.

 

Industrial  radio  frequency  interference  from  the  unit  meets  the  requirements  of  Grade 

Б

 

ГОСТ

 

Р

 51318.22 (

СИСПР

22-2006) Clauses 5.1, 6.1. 

1.2 13.

 

Ingress Protection Rating (if wall mounted): 

IP30 

1.2 14.

 

Pre-Operation Time: 

3 s max 

1.2 15.

 

The design of the unit provides its fire safety in emergency operation and under violation 

of operation rules in accordance with Russian Standard 

ГОСТ

 12.1.004-91. 

1.2 16.

 

The  content  of  precious  materials:  no  need  to  account  for  the  storage,  disposal  and 

recycling. 

1.3

 

Standard Delivery 

1)

 

S2000-KPB Executive Unit 

– 1 pc. 

2)

 

Instruction Manual 

– 1 pc.   

3)

 

DIN 7982 Flat Head Tapping Screw with Cross Drive 2.2

×

6.5 

– 1 pc. 

4)

 

Woodscrew 

– 3 pcs. 

5)

 

Wall Plug 6

×

30 

– 3 pcs. 

6)

 

Load Connection Module 

– 6 pcs. 

7)

 

Package 

– 1 pc. 

2

 

PERFORMANCE 

The unit can operate in the following modes: 

 

Quiescent; 

 

Power Failed; 

 

Device Failed. 

2.1

 

Quiescent Mode 

The unit being in the quiescent mode, its READY LED is lit steady. 

1.2 1.

 

Alarm Inputs of the Unit 

Each  of  the  two  inputs  of  the  unit  can  be  used  independently  to  monitor  conditions  of  fire 

protection  equipment  (for  example,  MASS  or  PRESSURE  outputs),  limit  switches,  detectors  and 
alarms including those which are not directly related to fire and intrusion alarm systems. In this case an 
alarm loop should be connected to the unit’s input. 

The  unit  measures  active  (linear,  ohmic)  resistance  in  its  alarm  loops  generating  relevant 

information and service messages and sending them to the network controller. 

Each input of the unit can be related with one of five different states depending on the value of the 

alarm loop resistance. These states and threshold values of resistance are programmable (see Section  
«Programming the Unit»). The layout of states and the positions of the threshold values between states 
relative to alarm loop resistance values are shown in Figure 1. 

A state of an input is changed when the resistance of the alarm loop connected to the input appears 

to be in a range related with any state other than the current one within a given time. 

For  such  “Restored”  states  as  Auxiliary  Input  Restored,  Battery  Restored  and  so  on  the  time  of 

transition is defined by a configuration parameter Restore Time of the unit input. 

For  the  Disarmed  and  Addressable  Loop  Parameter  Error  states  the  transition  time  is  not 

applicable. An input proceeds to this states immediately. 

For other states the time of transition (the integration time) is equal 300 ms. 

Summary of Contents for S2000-KPB

Page 1: ...1 2 4 The unit is designed to be installed on a vertical surface inside the protected premises closely to the executive devices The unit is designed for round the clock operation 1 2 5 The unit must not be used in aggressive medium or dust condition or in explosion hazardous premises 1 2 6 As to the resistance to mechanical stress the unit falls in the placement category 03 of ОСТ 25 1099 83 1 2 7...

Page 2: ... of the Unit Each of the two inputs of the unit can be used independently to monitor conditions of fire protection equipment for example MASS or PRESSURE outputs limit switches detectors and alarms including those which are not directly related to fire and intrusion alarm systems In this case an alarm loop should be connected to the unit s input The unit measures active linear ohmic resistance in ...

Page 3: ...l Temperature Tamper Restored Battery Restored Off Is defined by the Restore Time configuration parameter Auxiliary Input Alarm Green Pulses for 250 ms every 2 s 300 milliseconds Low Level Pump On Low Temperature Green Pulses once per four seconds Pump Off High Level High Temperature Green Pulses once per two seconds Auxiliary Input Alarm 2 Service Required Green Double flashes for 250 ms every 2 ...

Page 4: ...hould be given from the network controller to the unit The relevant input shall enter a state related with the current resistance of the alarm loop connected to the input If an error has occurred in the configuration parameters of an input the input proceeds to the Addressable Loop Parameter Error status For this status the unit doesn t generate messages when the resistance of the alarm loop chang...

Page 5: ...e specified time period The Control Delay parameter ranges from 0 to 8192 s 2 hours 16 minutes 32 s in increments of 0 125 s If Control Delay is missed or equal to zero the program starts running just after receiving the command Output control commands with the programs 5 6 7 and 8 Switch ON OFF can include detailed data defining a rate and pulse ration of switching the outputs If these data are m...

Page 6: ...ng for a Switched On Output Type of Monitoring The Types of Open Circuit Failure Monitoring for a Switched On Output 0 Disabled 1 Normal 2 Programmable Open Circuit Threshold 3 Periodic Load Shutdown 4 Current Drop Monitoring o For the Disabled monitoring type the S2000 KPB doesn t monitor the circuit for open failures when the output circuit is activated o For the Normal monitoring type the used ...

Page 7: ... diagram is shown in Figure 4 If a load doesn t allow short time shutting down the Programmable Open Circuit Threshold or Current Drop Monitoring monitoring types is suitable When a part of the monitored circuit with several executive devices is isolated and as a consequence the operating current has dropped below a programmed threshold the unit generates an Open Circuit message Current Drop Monit...

Page 8: ...t steady 2 Below the normal range for an input On On for 0 25 s and off for 1 75 s Off Lit steady 3 Below the normal range for both inputs On On for 0 25 s and off for 1 75 s Off On for 0 25 s and off for 1 75 s The internal circuits of the unit and output circuits are supplied with power by a power input with a higher voltage The values of the current consumed in various conditions are shown in t...

Page 9: ...device connected to the same interface RS 485 3 2 2 If a wrong address is assigned to the unit it can be reset to 127 without disconnecting from the RS 485 interface and connecting to a PC Remove the cover of the unit and perform the following combination of presses on the unit s tamper switch long long long short dash dash dash dot A long press means pressing the tamper switch and holding it pres...

Page 10: ...for the unit to monitor an activated output when an open circuit failure has occurred Any value from Table 4 Normal Open Circuit Failure Current The value of the minimum current in the monitored circuit for the monitoring type Programmable Open Circuit Threshold 5 mA to 2 5 A 5 mA Current Calibration Factor The value for estimating the current at the output This value is written to the memory of t...

Page 11: ...he unit s cover and perform the following combination of presses on the tamper switch short long short short dot dash dot dot A long press means pressing the tamper switch and holding it pressed for 0 5 to 1 5 second while a short press means pressing the tamper switch and holding it pressed for shorter than 0 5 s If pressing the combination has succeeded the unit resets with the base configuratio...

Page 12: ...hown devices 2 The load connection modules should be installed within the cases of executive devices except for discharge circuits 3 For discharge circuits and explosion protected devices the load connection modules can be located in the proximity of them 4 If an output is not in use a 1kOhm 0 5 W resistor can be used instead of the load connection module 5 Normally open and normally closed detect...

Page 13: ...red by a 12 V power supply R1 0 25 Ohm While powered by a 24 V power supply R1 0 34 Ohm The dependence between the resistance of a wire and its length for various cross sections is shown in Table 8 Table 8 The Dependence between the Resistance of the Wire and its Length Cross Section Cross Section mm2 Wire Resistance Ω Ω Ω Ω L 1 m L 2 m L 4 m L 6 m L 8 m L 10 m 0 2 0 0875 0 1750 0 3500 0 5250 0 70...

Page 14: ...nected wires doesn t exceed 0 3 Ohm the resistance of the exploder is 6 Ohm and the estimated current of the activation of the exploder is 0 1 A then the resistance value of the additional resistance should be 160 Ohm 4 9 If the circuit connected to an output is monitored neither for open circuit failure nor for short circuit failure the first type of monitored circuits no load connection module i...

Page 15: ...e RS 485 interface Which control programs are assigned to each output in the configuration chart of the unit Which events or commands of the network controller correspond to activation of the control program at each used unit s output How to generate the command or call the event to activate the control command for each used output 5 3 2 Open the cover of the S2000 KPB unit removing the tamper lab...

Page 16: ... for the used outputs 1 2 3 4 5 6 of the unit for which the unit s configuration specifies the function of monitoring open circuit failures 5 3 16 Ensure that on opening the circuit the status indicator of the relevant output double flashes in amber once per two seconds 5 3 17 Ensure that the control device the network controller displays the event of open circuit failure for the relevant address ...

Page 17: ...17 6 OVERALL AND MOUNTING DIMENSIONS ZAO NVP Bolid 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 775 7155 Email info bolid ru Technical Support support bolid ru http bolid ru ...

Reviews: