When release circuits or explosion protected devices are being connected to the S2000-KPB then the 
load  connection  modules  can  be  located  in  the  vicinity  of  the  connected  devices.  An  example  of 
connection diagram is shown in Figure 3. 

The  monitored  states  of  a  monitored  circuit  are  defined  by  the  circuit  failure  detection  type 

specified in the configuration parameters in accordance with Table 3. 

Table 3. The Types of Monitored Circuits 

Circuit Failure 

Detection Type 

Monitored Conditions 

No circuit condition is monitored 

The circuit is monitored for open failures 

The circuit is monitored for short failures 

The circuit is monitored both for open and short failures 

When a monitored circuit is switched off its conditions are defined by the voltage on the positive 

output terminal relative to the «0 V» terminal: 

 

«Open Circuit Failure»: less than minus 1.125 V; 

 

«Short Circuit Failure»: more than minus 0.15 V; 

 

«Norm»: between minus 0.15 V and minus 1.125 V; 

When a monitored circuit is switched on its conditions are defined by the current carrying through 

the circuit: 

 

«Short Circuit Failure»: More than 2.5A; 

 

«Norm»: Less than 2.5 A but more than open-circuit current; 

 

«Open  Circuit  Failure»:  The  value  of  the  open-circuit  current  is  defined  depending  on  the 
selected type of open-circuit failure monitoring in the unit configuration. The available variants 
are shown in the table below. 

 

Table 4. The Types of Monitoring for a Switched-On Output 

Type of 

Monitoring 

The Types of Open-Circuit Failure Monitoring for a Switched-On Output 

Disabled 

Normal 

Programmable Open-Circuit Threshold 

Periodic Load Shutdown 

Current Drop Monitoring 

o

 

For the Disabled monitoring type the S2000-KPB doesn’t monitor the circuit for open failures 

when the output circuit is activated. 

o

 

For the Normal monitoring type the used minimum value of the output current is 5 mA. 

o

 

For the Programmable Open-Circuit Threshold monitoring type the minimum output current is 

equal  to  an  Open-Circuit  Failure  Current  parameter  from  the  unit’s  configuration.  The  value  of  the 
parameter for each output can be set either while configuring the unit (see Section 3.3, Programming 
the Unit) or standalone without connecting to a personal computer. For doing so switch on the relevant 
outputs  and  ensure  that  all  the  connected  executive  devices  operate  properly.  Then  open  the  unit’s 
cover  and  perform  a  combination  of  presses  on  the  tamper  switch:  short,  long,  long,  long  (dot  dash 
dash dash). A long press means holding the tamper switch pressed for 0.5 to 1.5 second while a short 
press means holding the tamper switch pressed for shorter than 0.5 s. If pressing the combination has 
succeeded  than  for  each  active  output  the  unit  generates  a  value  of  the  Open-Circuit  Failure  Current 
parameter  less  by  eighth  than  the  current  value  of  output  current.  Also  the  Type  of  Open-Circuit 
Failure  Monitoring  is  changed  for  Programmable  Open-Circuit  Threshold  while  the  indicators  of  the 
relevant outputs pulse within 4 second in the mode “On for 0.75 s and off for 0.25 s”. 

Summary of Contents for S2000-KPB

Page 1: ...1 2 4 The unit is designed to be installed on a vertical surface inside the protected premises closely to the executive devices The unit is designed for round the clock operation 1 2 5 The unit must not be used in aggressive medium or dust condition or in explosion hazardous premises 1 2 6 As to the resistance to mechanical stress the unit falls in the placement category 03 of ОСТ 25 1099 83 1 2 7...

Page 2: ... of the Unit Each of the two inputs of the unit can be used independently to monitor conditions of fire protection equipment for example MASS or PRESSURE outputs limit switches detectors and alarms including those which are not directly related to fire and intrusion alarm systems In this case an alarm loop should be connected to the unit s input The unit measures active linear ohmic resistance in ...

Page 3: ...l Temperature Tamper Restored Battery Restored Off Is defined by the Restore Time configuration parameter Auxiliary Input Alarm Green Pulses for 250 ms every 2 s 300 milliseconds Low Level Pump On Low Temperature Green Pulses once per four seconds Pump Off High Level High Temperature Green Pulses once per two seconds Auxiliary Input Alarm 2 Service Required Green Double flashes for 250 ms every 2 ...

Page 4: ...hould be given from the network controller to the unit The relevant input shall enter a state related with the current resistance of the alarm loop connected to the input If an error has occurred in the configuration parameters of an input the input proceeds to the Addressable Loop Parameter Error status For this status the unit doesn t generate messages when the resistance of the alarm loop chang...

Page 5: ...e specified time period The Control Delay parameter ranges from 0 to 8192 s 2 hours 16 minutes 32 s in increments of 0 125 s If Control Delay is missed or equal to zero the program starts running just after receiving the command Output control commands with the programs 5 6 7 and 8 Switch ON OFF can include detailed data defining a rate and pulse ration of switching the outputs If these data are m...

Page 6: ...ng for a Switched On Output Type of Monitoring The Types of Open Circuit Failure Monitoring for a Switched On Output 0 Disabled 1 Normal 2 Programmable Open Circuit Threshold 3 Periodic Load Shutdown 4 Current Drop Monitoring o For the Disabled monitoring type the S2000 KPB doesn t monitor the circuit for open failures when the output circuit is activated o For the Normal monitoring type the used ...

Page 7: ... diagram is shown in Figure 4 If a load doesn t allow short time shutting down the Programmable Open Circuit Threshold or Current Drop Monitoring monitoring types is suitable When a part of the monitored circuit with several executive devices is isolated and as a consequence the operating current has dropped below a programmed threshold the unit generates an Open Circuit message Current Drop Monit...

Page 8: ...t steady 2 Below the normal range for an input On On for 0 25 s and off for 1 75 s Off Lit steady 3 Below the normal range for both inputs On On for 0 25 s and off for 1 75 s Off On for 0 25 s and off for 1 75 s The internal circuits of the unit and output circuits are supplied with power by a power input with a higher voltage The values of the current consumed in various conditions are shown in t...

Page 9: ...device connected to the same interface RS 485 3 2 2 If a wrong address is assigned to the unit it can be reset to 127 without disconnecting from the RS 485 interface and connecting to a PC Remove the cover of the unit and perform the following combination of presses on the unit s tamper switch long long long short dash dash dash dot A long press means pressing the tamper switch and holding it pres...

Page 10: ...for the unit to monitor an activated output when an open circuit failure has occurred Any value from Table 4 Normal Open Circuit Failure Current The value of the minimum current in the monitored circuit for the monitoring type Programmable Open Circuit Threshold 5 mA to 2 5 A 5 mA Current Calibration Factor The value for estimating the current at the output This value is written to the memory of t...

Page 11: ...he unit s cover and perform the following combination of presses on the tamper switch short long short short dot dash dot dot A long press means pressing the tamper switch and holding it pressed for 0 5 to 1 5 second while a short press means pressing the tamper switch and holding it pressed for shorter than 0 5 s If pressing the combination has succeeded the unit resets with the base configuratio...

Page 12: ...hown devices 2 The load connection modules should be installed within the cases of executive devices except for discharge circuits 3 For discharge circuits and explosion protected devices the load connection modules can be located in the proximity of them 4 If an output is not in use a 1kOhm 0 5 W resistor can be used instead of the load connection module 5 Normally open and normally closed detect...

Page 13: ...red by a 12 V power supply R1 0 25 Ohm While powered by a 24 V power supply R1 0 34 Ohm The dependence between the resistance of a wire and its length for various cross sections is shown in Table 8 Table 8 The Dependence between the Resistance of the Wire and its Length Cross Section Cross Section mm2 Wire Resistance Ω Ω Ω Ω L 1 m L 2 m L 4 m L 6 m L 8 m L 10 m 0 2 0 0875 0 1750 0 3500 0 5250 0 70...

Page 14: ...nected wires doesn t exceed 0 3 Ohm the resistance of the exploder is 6 Ohm and the estimated current of the activation of the exploder is 0 1 A then the resistance value of the additional resistance should be 160 Ohm 4 9 If the circuit connected to an output is monitored neither for open circuit failure nor for short circuit failure the first type of monitored circuits no load connection module i...

Page 15: ...e RS 485 interface Which control programs are assigned to each output in the configuration chart of the unit Which events or commands of the network controller correspond to activation of the control program at each used unit s output How to generate the command or call the event to activate the control command for each used output 5 3 2 Open the cover of the S2000 KPB unit removing the tamper lab...

Page 16: ... for the used outputs 1 2 3 4 5 6 of the unit for which the unit s configuration specifies the function of monitoring open circuit failures 5 3 16 Ensure that on opening the circuit the status indicator of the relevant output double flashes in amber once per two seconds 5 3 17 Ensure that the control device the network controller displays the event of open circuit failure for the relevant address ...