background image

 

5

1.2 2.

 

Outputs 

The  S2000-KPB  provides  control  for  connected  executive  devices  by  switching  power  voltage 

from  the  unit’s  terminals  U

main

  and  U

back

  to  the  terminals  of  the  outputs.  Connecting  external  power 

supplies is prohibited and can damage the unit. 

The S2000-KPB provides switching on (switching off, pulsing) for its outputs in accordance with 

assigned  control  programs  on  receiving  control  commands  over  the  RS-485  interface.  The  unit  also 
provides monitoring executive outputs and the monitored circuits connected to the outputs. 

The available programs for executive outputs are shown in Table 2. 

Table 2. Commands to Control Outputs 

Program 

Number 

Program Description 

Final State 

Return the output to the initial condition 

− 

Switch ON (until a new command is received) 

− 

Switch OFF (until a new command is received) 

− 

Switch ON for a given time, then switch OFF 

Off 

Switch OFF for a given time, then switch ON 

On 

5, 6 

Switch ON/OFF (until a new command is received) 

− 

Switch ON/OFF for a given time, then switch OFF 

Off 

Switch ON/OFF for a given time, then switch ON 

On 

11 

Discharge extinguishing agent 

Off 

Note: 

The  full  list  of  output  executive  commands  can  be  seen  in  the  User’s  Manual  for  an 

S2000M  panel.  When  the  S2000-KPB  is  connected  to  the  internal  interface  RS-485-2  of  an  S2000-
ASPT  unit,  the  first  one  is  used  to  expand  the  discharge  circuits  of  the  last  one.  In  this  case  the 
individual outputs of the unit cannot be controlled remotely from the S2000M panel

The  output  executive  commands  can  comprise  the  Control  Delay  parameter.  In  such  case  the 

program  starts  running  after  expiration  of  the  specified  time  period.  The  Control  Delay  parameter 
ranges from 0 to 8192 s (2 hours 16 minutes 32 s) in increments of 0.125 s. If Control Delay is missed 
or equal to zero, the program starts running just after receiving the command. 

Output  control  commands  with  the  programs  #5,  #6,  #7,  and  #8 (Switch  ON/OFF)  can  include 

detailed  data  defining  a  rate  and  pulse  ration  of  switching  the  outputs.  If  these  data  are  missed  in  a 
command, the output will be switched on and off with 1 Hz frequency and pulse ratio of 2. 

Output control commands with the programs #3, #4, #7, #8 («Switch for a Given Time») contain 

the Control Time parameter. The Control Time can have a value from 0 to 8192 s (2 hours 16 minutes 
and 32 s) in the increments of 0.125 s. 

If Control Time is missed in a command then the program will be executed within the time given 

in the unit’s configuration parameter Discharge Time. 

If Control Time in a command is equal to zero, the output will be switched to the initial status for 

the received command. 

In case of  an output control command with the program #11 the unit generates a discharge pulse 

for the relevant output (the output is switched on for a given time and then the output is switched off). 
If  the  command  contains  zero  as  the  number  of  output,  a  discharge  pulse  will  be  generated  for  all 
outputs one-by-one. 

If  a  command  contains  no  Control  Time  or  no  Control  Delay,  the  values  for  them  will  be  taken 

from the unit’s configuration. 

The value of discharge interval time is given by the relevant configuration parameter. 
The unit provides monitoring of lines of connection of executive  devices (the monitored circuits) 

provided  that  termination  elements  -  load  connection  modules  are  brought  into  the  lines.  The  load 
connection modules are installed inside the executive device enclosures (except for the release circuit). 

Summary of Contents for S2000-KPB

Page 1: ...1 2 4 The unit is designed to be installed on a vertical surface inside the protected premises closely to the executive devices The unit is designed for round the clock operation 1 2 5 The unit must not be used in aggressive medium or dust condition or in explosion hazardous premises 1 2 6 As to the resistance to mechanical stress the unit falls in the placement category 03 of ОСТ 25 1099 83 1 2 7...

Page 2: ... of the Unit Each of the two inputs of the unit can be used independently to monitor conditions of fire protection equipment for example MASS or PRESSURE outputs limit switches detectors and alarms including those which are not directly related to fire and intrusion alarm systems In this case an alarm loop should be connected to the unit s input The unit measures active linear ohmic resistance in ...

Page 3: ...l Temperature Tamper Restored Battery Restored Off Is defined by the Restore Time configuration parameter Auxiliary Input Alarm Green Pulses for 250 ms every 2 s 300 milliseconds Low Level Pump On Low Temperature Green Pulses once per four seconds Pump Off High Level High Temperature Green Pulses once per two seconds Auxiliary Input Alarm 2 Service Required Green Double flashes for 250 ms every 2 ...

Page 4: ...hould be given from the network controller to the unit The relevant input shall enter a state related with the current resistance of the alarm loop connected to the input If an error has occurred in the configuration parameters of an input the input proceeds to the Addressable Loop Parameter Error status For this status the unit doesn t generate messages when the resistance of the alarm loop chang...

Page 5: ...e specified time period The Control Delay parameter ranges from 0 to 8192 s 2 hours 16 minutes 32 s in increments of 0 125 s If Control Delay is missed or equal to zero the program starts running just after receiving the command Output control commands with the programs 5 6 7 and 8 Switch ON OFF can include detailed data defining a rate and pulse ration of switching the outputs If these data are m...

Page 6: ...ng for a Switched On Output Type of Monitoring The Types of Open Circuit Failure Monitoring for a Switched On Output 0 Disabled 1 Normal 2 Programmable Open Circuit Threshold 3 Periodic Load Shutdown 4 Current Drop Monitoring o For the Disabled monitoring type the S2000 KPB doesn t monitor the circuit for open failures when the output circuit is activated o For the Normal monitoring type the used ...

Page 7: ... diagram is shown in Figure 4 If a load doesn t allow short time shutting down the Programmable Open Circuit Threshold or Current Drop Monitoring monitoring types is suitable When a part of the monitored circuit with several executive devices is isolated and as a consequence the operating current has dropped below a programmed threshold the unit generates an Open Circuit message Current Drop Monit...

Page 8: ...t steady 2 Below the normal range for an input On On for 0 25 s and off for 1 75 s Off Lit steady 3 Below the normal range for both inputs On On for 0 25 s and off for 1 75 s Off On for 0 25 s and off for 1 75 s The internal circuits of the unit and output circuits are supplied with power by a power input with a higher voltage The values of the current consumed in various conditions are shown in t...

Page 9: ...device connected to the same interface RS 485 3 2 2 If a wrong address is assigned to the unit it can be reset to 127 without disconnecting from the RS 485 interface and connecting to a PC Remove the cover of the unit and perform the following combination of presses on the unit s tamper switch long long long short dash dash dash dot A long press means pressing the tamper switch and holding it pres...

Page 10: ...for the unit to monitor an activated output when an open circuit failure has occurred Any value from Table 4 Normal Open Circuit Failure Current The value of the minimum current in the monitored circuit for the monitoring type Programmable Open Circuit Threshold 5 mA to 2 5 A 5 mA Current Calibration Factor The value for estimating the current at the output This value is written to the memory of t...

Page 11: ...he unit s cover and perform the following combination of presses on the tamper switch short long short short dot dash dot dot A long press means pressing the tamper switch and holding it pressed for 0 5 to 1 5 second while a short press means pressing the tamper switch and holding it pressed for shorter than 0 5 s If pressing the combination has succeeded the unit resets with the base configuratio...

Page 12: ...hown devices 2 The load connection modules should be installed within the cases of executive devices except for discharge circuits 3 For discharge circuits and explosion protected devices the load connection modules can be located in the proximity of them 4 If an output is not in use a 1kOhm 0 5 W resistor can be used instead of the load connection module 5 Normally open and normally closed detect...

Page 13: ...red by a 12 V power supply R1 0 25 Ohm While powered by a 24 V power supply R1 0 34 Ohm The dependence between the resistance of a wire and its length for various cross sections is shown in Table 8 Table 8 The Dependence between the Resistance of the Wire and its Length Cross Section Cross Section mm2 Wire Resistance Ω Ω Ω Ω L 1 m L 2 m L 4 m L 6 m L 8 m L 10 m 0 2 0 0875 0 1750 0 3500 0 5250 0 70...

Page 14: ...nected wires doesn t exceed 0 3 Ohm the resistance of the exploder is 6 Ohm and the estimated current of the activation of the exploder is 0 1 A then the resistance value of the additional resistance should be 160 Ohm 4 9 If the circuit connected to an output is monitored neither for open circuit failure nor for short circuit failure the first type of monitored circuits no load connection module i...

Page 15: ...e RS 485 interface Which control programs are assigned to each output in the configuration chart of the unit Which events or commands of the network controller correspond to activation of the control program at each used unit s output How to generate the command or call the event to activate the control command for each used output 5 3 2 Open the cover of the S2000 KPB unit removing the tamper lab...

Page 16: ... for the used outputs 1 2 3 4 5 6 of the unit for which the unit s configuration specifies the function of monitoring open circuit failures 5 3 16 Ensure that on opening the circuit the status indicator of the relevant output double flashes in amber once per two seconds 5 3 17 Ensure that the control device the network controller displays the event of open circuit failure for the relevant address ...

Page 17: ...17 6 OVERALL AND MOUNTING DIMENSIONS ZAO NVP Bolid 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 775 7155 Email info bolid ru Technical Support support bolid ru http bolid ru ...

Reviews: