If the combination of presses is performed incorrectly, do nothing for two seconds and try pressing again. 

To  get  more  information  about  setting  addresses  of  the  devices  connected  into  the  polling  loop  please  refer  to  the 
manuals for S2000-KDL, S2000M panel, and Orion Pro Workstation. 

WALK TEST 

Connect  the  detector  to  the  multiplex  addressable  polling  loop  as  shown  in  Figure  4.  Then  power  on  the  controller  and 

wait for about two minutes. Next, walk through the detection zone. The detector shall issue an alarm after your three or 

four  steps,  with  its  LED  being  flashing.  Wait  until  the  LED  finishes  flashing,  and  then  continue  crossing  the  detection 

zone. The detector should issue an alarm. If nobody is moving within the detection zone, no alarms shall be issued. 

WARNING 

 

To ensure proper operation, walk test the S2000-IK rev.02 annually as described above.

 

ENABLING/DISABLING LED INDICATION 

LED indication can be controlled either via a PC or by means of the detector tamper switch

If  LED  indication  is  to  be  controlled  via  a  PC,  by  the  connected  S2000-KDL,  the  S2000-KDL  should  be  specifically 

configured from the PC using the UProg Configuration Tool. The parameter Device Indication Control of the S2000-KDL 

polling  loop  input  zone  which  is  assigned  to  the  S2000-IK  rev.02  should  be  set  to  a  proper  value.  The  value  can  be  0 

(indication  is  inhibited),  1  (local  indication),  or  2  (indication  controlled  remotely  by  the  PL  controller).  By  default,  Device 

Indication Control is set to the value of 1, providing LED indication in accordance with the detector’s own pre-determined 

algorithm. To disable indication, set this parameter to zero. 

If LED indication is to be defined using the tamper switch, the algorithm is as follows. A combination of presses LLSS – 

L stands  for  a  long  press  (longer  than  0.5  s)  and  S  stands  for  a  short  press  (shorter  than  0.5 s),  with  pauses  between 

presses each being less than 1 s - switches the detector to the mode of local controlling. A combination of presses LLSL 

switches the indication off for 5 minutes. In 5 minutes the indication starts be controlled as set in the configuration for this 

address point. 