If the combination of presses is performed incorrectly, do nothing for two seconds and try pressing again.
To get more information about setting addresses of the devices connected into the polling loop please refer to the
manuals for S2000-KDL, S2000M panel, and Orion Pro Workstation.
WALK TEST
Connect the detector to the multiplex addressable polling loop as shown in Figure 4. Then power on the controller and
wait for about two minutes. Next, walk through the detection zone. The detector shall issue an alarm after your three or
four steps, with its LED being flashing. Wait until the LED finishes flashing, and then continue crossing the detection
zone. The detector should issue an alarm. If nobody is moving within the detection zone, no alarms shall be issued.
WARNING
To ensure proper operation, walk test the S2000-IK rev.02 annually as described above.
ENABLING/DISABLING LED INDICATION
LED indication can be controlled either via a PC or by means of the detector tamper switch.
If LED indication is to be controlled via a PC, by the connected S2000-KDL, the S2000-KDL should be specifically
configured from the PC using the UProg Configuration Tool. The parameter Device Indication Control of the S2000-KDL
polling loop input zone which is assigned to the S2000-IK rev.02 should be set to a proper value. The value can be 0
(indication is inhibited), 1 (local indication), or 2 (indication controlled remotely by the PL controller). By default, Device
Indication Control is set to the value of 1, providing LED indication in accordance with the detector’s own pre-determined
algorithm. To disable indication, set this parameter to zero.
If LED indication is to be defined using the tamper switch, the algorithm is as follows. A combination of presses LLSS –
L stands for a long press (longer than 0.5 s) and S stands for a short press (shorter than 0.5 s), with pauses between
presses each being less than 1 s - switches the detector to the mode of local controlling. A combination of presses LLSL
switches the indication off for 5 minutes. In 5 minutes the indication starts be controlled as set in the configuration for this
address point.