background image

INSTALLING THE DETECTOR 

1.  Using  a  screwdriver  remove  the  locking  screw  in  the  lower  part  of 

the rear housing (see Figure 2) and separate the front housing. 

2.  Using a screwdriver remove the screw keeping the PCB and lift the 

PCB out of the rear housing. 

3.  Drill  out  the  required  mount  and  wiring  holes  in  the  rear  housing 

(see Figure 2). 

4.  Having  selected  the  mounting  location,  mark  the  positions  of  the 

fixing  holes  on  the  wall  taking  into  account  positions  of  mounting 
holes in  the rear housing or mount bracket (see Figure 3) and drill 
holes at the marked places. 

5.  Slide  the  wires  into  the  wire  holes  in  the  mount  bracket  or  rear 

housing. 

6.  Leave some centimeters of each wire for connecting to the terminal 

blocks. 

7.  Attach  the  rear  housing  or  mount  bracket  at  the  selected  location. 

For  mounting  with  the  swivel  mounting  bracket,  unscrew  the  bolt 
from  the  ball-joint  (see  Figure 3)  and  align  the  square  part  of  the 
ball-joint  with  the  relevant  notch  in  the  upper  part  of  the  rear 
housing.  Insert  the  bolt  into  the  hole  at  the  upper  part  of  the  rear 
housing,  turn  the  rear  housing  to  the  proper  position,  and  tighten 
the bolt. 

8.  Finally, place the PCB and tighten the PCB screw. 

Note: To prevent false alarms due to animals reliably, the detector 
shall not be deflected relative to the vertical direction by more than 
two degrees. 

 

 

Figure 2: Rear Housing of the Detector 

 

Figure 3: Mount Bracket Structure

 

WIRING 

 

Figure  4  shows  the  way  to  connect  detector’s  PL 
contacts  which  are  situated  at  the  top  of  its  PCB 
to the relevant contacts of the S2000-KDL. 

Figure 5 shows the wiring diagram for connecting 
the  detector  to  the  multiplex  addressable  polling 
loop of the S2000-KDL controller which is in turns 
connected to the network controller and the power 
supply. 

 

 

Figure 4. Connection Terminals 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5. Connecting the Detector for Testing and Operation

 

PROGRAMMING 

The detector comes with the address of 127. The address of the detector within the polling loop is stored in the detector’s 
microprocessor non-volatile memory (EEPROM). The address ranges from 1 to 127. 

To change the detector address, send the Change Device Address command from the network controller with the old and 
new  addresses  of  the  detector  as  parameters.  Observe  the  messages  about  disconnecting  the  detector  with  the  old 
address and connecting the detector with the new address displayed by the network controller. 

If two or more detectors have the same addresses then use the Set Device Address command. For doing so, send this 
command  specifying  the  new  address  from  the  network  controller.  Then  remove  the  front  housing  and  ensure  the 
detector  has  entered  the  programming  mode  indicating  this  by  LED’s  flickering  once  per  2  seconds.  Next,  perform  a 
combination of presses on the detector’s tamper switch – LLLS, where “L” is for a long press (longer than 0.5 s) and “S” is 
for  a  short  press  (shorter  than  0.5 s).  A  pause  between  presses  shall  not  exceed  1 s.  Changing  the  address  shall  be 
confirmed  by  steady  illumination  of  the  LED  which  indicates  detector‘s  software  reset;  and  the  network  controller  shall 
display a message about connecting the detector with the newly programmed address. 

GND 

+12 V 

S2000(M) 

Power Supply 

GND 

+12 V 

S2000-IK 

−−−−

PL 

+PL 

−−−−

PL 

+PL 

+U 

GND 

S2000-KDL 

RS-485A 

RS-485B 

Reviews: