background image

7.   In the premises where the detector is to be installed, for the time of protection all the windows, air-vents, balcony 

doors, etc. must be closed; all ventilators, heaters, air conditioners must be switched off; and there should not be 
any birds or animals. 

8.  Non-transparent  objects  in  the  detection  area  (such  as  cabinets,  room  dividers,  etc.)  as  well  as  glass  or  mesh 

partitions  obscure  the  detection  and  result  in  forming  of  dead  zones  through  which  human’s  moving  can  be  not 
detected. 

The recommended mounting height for the detector is 2.1 meters above the floor. 

WIRING THE DETECTOR 

ATTENTION!!! 

Summarized current consumption of all the addressable devices connected to an S2000-KDL must not exceed 65 
milliamperes. If, for example, the polling loop of the S2000-KDL comprises only S2000-IK rev.03 detectors, their 
maximum number will be equal to: 

 

 

.  

  .

 

Parameters of the polling loop must correlate with parameters described in the manual of the S2000-KDL. 

You can check the correctness of the mounting and the correctness of the estimated number of the detectors to 
be  connected  to  the  polling  loop  by  requesting  for  the  value  of  the  polling  loop  voltage  at  the  location  of  the 
detector by means of UProg Configuration Tool. This value must be above 7 V. 

Figure 1 shows the typical schematic of wiring the detector to the multiplex addressable polling loop of an S2000-KDL. In 
the S2000-KDL configuration the detector’s type should be specified as 5 (Intrusion with Tamper Check) or 7 (Entrance) – 
please see S2000-KDL User’s Manual. 

 

 

 

 

 

 

 

 

 

 

 

Figure 1. Detector’s Wiring Diagram

 

PROGRAMMING 

The S2000-IK rev.03 to operate properly within two-wire addressable polling loop of the S2000-KDL controller, it must be 

assigned to a unique number in the range of 1 to 127 within the loop – the address which is stored in the S2000-IK rev.03 

non-volatile memory (EEPROM). An S2000-IK rev.03 is supplied with the default address of 127. This address value can 

be changed using either S2000(M) console tools or PC tools such as UProg Configuration Tool. 

In  order  to  program  the  unique  S2000-IK  rev.03  loop  address,  connect  it  to  a  S2000-KDL  controller  which  is  in  turns 

connected  to  a  network  controller  (an  S2000(M)  console  or  PC  under  UProg  software).  Then  send  one  of  the  following 

commands to the S2000-KDL controller (for getting more information see the relevant User’s Manual): 

Change the Device Address 

Use the Change Device Address command specifying the old detector address and the 

new  detector  address  as  the  parameters  (see  more  information  in  the  referred 

Manuals).  The  network  controller  will  display  the  messages  about  disconnecting  the 

device  with  the  old  address  and  then  detecting  the  device  with  newly  programmed 

address. Mark down the assigned address on the marking field of the detector. 

GND 

+12 V 

S2000(M) 

Power Supply 

GND 

+12 V 

S2000-IK 

−−−−

PL 

+PL 

−−−−

PL 

+PL 

+U 

GND 

S2000-KDL 

RS-485A 

RS-485B 

Summary of Contents for S2000-IK Rev.03

Page 1: ... Light Immunity Better than 6500 Lux Sabotage Resistant Zone Yes Operating Temperatures 30 to 50 C Humidity Up to 95 at 25 C non condensing Overall Dimensions H x W x D 68 mm 93mm 41 mm max Weight 125 gram max STANDARD DELIVERY Find the following unpacking the S2000 IK rev 03 S2000 IK rev 03 detector This Instruction Manual Two woodscrews 3 5 30 Two wall plugs 6 30 Two tapping screws 2 2 6 5 Brack...

Page 2: ...oop of an S2000 KDL In the S2000 KDL configuration the detector s type should be specified as 5 Intrusion with Tamper Check or 7 Entrance please see S2000 KDL User s Manual Figure 1 Detector s Wiring Diagram PROGRAMMING The S2000 IK rev 03 to operate properly within two wire addressable polling loop of the S2000 KDL controller it must be assigned to a unique number in the range of 1 to 127 within ...

Page 3: ...enabled To disable indication press the tamper switch in LLSL pattern otherwise to enable indication press the tamper switch in LLSS pattern where L stands for a long pressing longer than 0 5 s while S stands for a short pressing shorter than 0 5 s Pauses between pressings must not exceed 1 s each WALK TEST The detector having been connected to the polling loop its LED lights up indicating its sta...

Page 4: ...In no case shall seller be liable to anyone for any consequential or incidental damages for breach of this or any other warranty express or implied or upon any other basis of liability whatsoever even if the loss or damage is caused by the seller s own negligence or fault Some countries do not allow limitation on how long an implied warranty lasts or the exclusion or limitation of incidental or co...

Reviews: