11
Partition Condition
“1” – “60” LEDs Performance
Free Access
Blinks in green with 0.5 s on and 0.5 s off
Controlled Access
Lit steady with green
Disabled
Lit steady with amber
Note: S2000M Fire and Alarm Control Panel of ver.3.00 or higher shall be in use.
1.4.5
General indicators Fire 2, Fire, Prealarm, Intrusion, Panic Alarm, Arming Failed, Disabled,
Fault indicate alarms and troubles from the partitions “1” – “60” occurred currently. These LEDs pulse
synchronously with indicators of partitions which are in the relevant states. Thus, if several partitions
are in various conditions then these indicators provide fast estimation of current situation and defining
action priority. Table 16 describes performance of the indicators after alarms have been received.
Table 1.4.15.
Performance of Single-Color LEDs
Partition Condition
LED
Performance
Fire 2
FIRE 2
Lit steady with red
Fire
FIRE
Red: 0.25 s on / 0.25 s off
Fire Prealarm
PREALARM
Red: 0.25 s on / 1.75 s off
Intrusion Alarm,
Flooding Detected
INTRUSION
Red: 0.5 s on / 0.5 s off
Panic Alarm, Duress
PANIC ALARM
Red: 0.5 s on / 0.5 s off
Arming Failed
ARMING FAILED
Amber 0.5 s on and 0.5 s off
Disabled
DISABLED
Amber
Fault
FAULT *
Amber: 0.25 s on / 1.75 s off
Silenced
Amber
Note: * The FAULT LED indicates also loss of communication with the network controller.
The single-color LEDs are meant to indicate integrated conditions of partitions in scope of the
module. Summarized conditions with respect to the whole system are to be indicated by the related
S2000M.
Table 1.4.16.
Reader LED Performance
Operation Condition
LED Performance
Waiting for Response…
Flashes with red and green alternately
Operation Permitted
Lit steady with green
Access Denied
Pulses with red within a second: 0.125 s on / 0.125 s off