RATIO.pm6.5 - USA
Page 1.24
RATIO
BOGE – RATIO compressor control for screw compressors
Fault messages of the control system
1.7
Control unit
29
Key Enter
↵
does not open
Control unit defective
Replace control unit
Control unit
25
EPROM /recon-
ciliation error
Error loading software.
Control unit defective
Reload software or replace control unit
Control unit
26
Key (Off) O
does not open
Control unit defective
Replace control unit
Control unit
27
Key
i
does not open
Control unit defective
Replace control unit
Control unit
28
Key (ON) I
does not open
Control unit defective
Replace control unit
Control unit
30
Key
does not open
Control unit defective
Replace control unit
Control unit
31
Key
does not open
Control unit defective
Replace control unit
Network pressure trans-
mitter defective or wire
breakage
Replace network pressure transmitter or
re-establish electrical connection
Network press.
32
transmitter
faulty
Master
18
control
defective
Master control defective
Check supply voltage of master control.
Parameterization of external output enable
RATIO
FAULT
Rectification
Possible cause
System press.
33
transmitter
faulty
System pressure trans-
mitter defective or wire
breakage
Replace system pressure transmitter or
re-establish electrical connection
System press.
34
transmitter
faulty
System pressure trans-
mitter faulty
Replace system pressure transmitter