Note:
The drive is
factory set to the
Automatic Start Mode.
For Manual Start/Rest,
see Section 9.6, on
pages 33 and 34.
13 TRIMPOT ADJUSTMENTS
The drive contains trimpots
which are factory set for
most applications. See
Figure 4, on page 20, for the
location of the trimpots and
their approximate factory
calibrated positions. Some
applications may require
readjustment of the trimpots
in order to tailor the drive for
a specific requirement. The trimpots may be readjusted as described below.
WARNING! If possible, do not adjust trimpots with the main power applied. If
adjustments are made with the main power applied, an insulated adjustment
tool must be used and safety glasses must be worn. High voltage exists in this drive. Fire
and/or electrocution can result if caution is not exercised. Safety Warning, on pages 8 and
9, must be read and understood before proceeding.
38
Drive Operating Condition
Flash Rate
1
and LED Color
Normal Operation
Slow Flash Green
Overload (120% – 160% Full Load)
Steady Red
2
I
2
t (Drive Timed Out)
Quick Flash Red
Short Circuit
Slow Flash Red
Undervoltage
Quick Flash Red / Yellow
3
Overvoltage
Slow Flash Red / Yellow
3
Stop
Steady Yellow
TABLE 4 – DRIVE OPERATING CONDITION & STATUS LED INDICATOR
Notes: 1.
Slow Flash = 1 second on and 1 second off. Quick Flash = 0.25
second on and 0.25 second off.
2.
In Manual Start Mode, when the Overload
is removed, before the I
2
t times out and trips the drive, the “ST” LED will
flash green.
3.
In Manual Start Mode, when the Undervoltage or Overvoltage
condition is corrected, the “ST” LED will flash Red / Yellow / Green.