background image

 

 

 

 

2. INTRODUCTION & SPECIFICATION

 

This heater produces a totally dry heat, no condensation, no gas, no fumes. It reaches maximum heat output within a minute from being turned on. It 
is quick and easy to install reducing installation costs. Used with the CS-1 controller it can provide low / high heat or fan only settings.

  

Model 

860T 

Power 

6000W 

Input supply 

220-240V 

Dimensions (W x D x H) 

1105 x 108 x 225mm 

Weight 

14kg 

Recommended Mounting Height 

1.8 - 3.0M 

Safety Distance from Heater 

1.5M 

Optional Controller Model Number 

CS-1 

 

3. LOCATION OF HEATER 

When used as a space heater it should be mounted at a height of 1.8 

– 3m above floor level and a minimum of 300mm from the ceiling and adjacent 

walls. 

We do not recommend the 860T be used as an overdoor heater on an external door as the built-in thermostat can be unnecessarily activated when 
the outside door is opened. 

When used above an internal doorway, the heater can be wall or ceiling mounted at a height of 1.8 

– 3m above floor level and a minimum of 300mm 

from adjacent walls. 

4. MOUNTING INSTALLATION 

 

 

IMPORTANT! 

DO NOT mount heater directly below the socket outlet. 

 

IMPORTANT!

 Ensure that the mounting surface / ceiling supports are capable of taking the weight of the heater. 

 

IMPORTANT! 

Do not allow any object to come closer than 1.5m to the heater outlet. 

 

IMPORTANT! 

Always mount the heater horizontal mounting at any other angle will reduce the heater

’s life and invalidate the guarantee. 

 

IMPORTANT! 

The air intake and discharge areas must be kept completely clear for a minimum of 1.5m from the front of the heater. 

 

4.1 

MOUNTING KIT 

The mounting kit supplied with each heater consists of the following items. 
1 x Fixing Plate (approximately the same length as the heater), 2 x Small Side Brackets, 2 x Large Side Brackets, 2 x Plastic Domes 
4 x M2.9 Self Tapping Screws, 6 x M4 x 10mm Long Pozi Drive Screws and 2 x M4 Lock washers. 

 

4.2 

WALL MOUNTING ABOVE AN INTERNAL DOORWAY 

Attach the two Small Side brackets to the heater using the Plastic Domes and M2.9 Screws. Make sure both open slots are facing downwards 
and the brackets face towards the back of the heater (see Pic 1). 

Securely attach the Fixing Plate to the wall. Partially insert M4 screws into the outer two holes in each end of the bracket. Make sure the screw 
goes all the way through and the thread is just showing the other side (see Pic 2). The heater with its two end brackets should now be slotted 
onto the fixing bracket (see Pic 3). Now tighten up the four end screws and add an additional M4 centre screw and lock washer into the centre 
hole at each end of the fixing bracket (see Pic 4). UNDER NO CIRCUMSTANCES MUST THE HEATER BE TURNED ON IF THESE TWO 
CENTRE SCREWS AND LOCK WASHERS ARE NOT PRESENT OR TIGHTENED UP. 

 
 

4.3 

CEILING MOUNTING ABOVE AN INTERNAL DOORWAY 

You  can  either  use  M8  drop  rods  in the  two  threaded  holes  in the  top  of  the  heater  (drop  rods  not  supplied)  or 
mount directly to the ceiling using the supplied brackets. If mounting using the supplied brackets use the method 
(section  4.2)  above  with  the  exception  that  you  use  the  Large  Side  Brackets  and  they  must  face  upwards  (see 
Pic5). Do not switch on unless the 2 centre screws and lock washers are fitted to the side brackets and tightened. 

 

4.4 

WALL MOUNTING FOR SPACE HEATING 

The  mounting  method  is  the  same  as  described  above  (section  4.2)  above  with  the 

exception that you use the Large Side Brackets and they must face backwards (see 
Pic  6).  Do  not  switch  on  unless  the  2  centre  screws  and  lock  washers  are  fitted  to 
the  side  brackets  and  tightened.  The  angle  of  the  heater  can  be  adjusted  by 
releasing the Plastic Domes by unscrewing the self-tapping screws a half turn twist 
the  heater  to  required  angle  then  tighten  up  the  screws.  The  heater  may  only  be 
used between 90° (horizontal) and 180° (vertically downwards).

 

 

Pic 1 

Pic 2 

Pic 3 

Pic 4 

Pic 5 

Lock Washer 

Pic 6 

CS-1 Controller 

(Optional Extra) 

Summary of Contents for 860T

Page 1: ...tly rated fuse is fitted DO NOT use worn or damaged cables plugs or connectors Immediately have any faulty item repaired or replaced by a qualified electrician The unit should be protected by a suitably rated isolator and fuse or MCB This heater is IP20 rated and is suitable for indoor or under cover use only Do not attach this heater to an extension cord it must be hard wired in position 1 2 GENE...

Page 2: ...zi Drive Screws and 2 x M4 Lock washers 4 2 WALL MOUNTING ABOVE AN INTERNAL DOORWAY Attach the two Small Side brackets to the heater using the Plastic Domes and M2 9 Screws Make sure both open slots are facing downwards and the brackets face towards the back of the heater see Pic 1 Securely attach the Fixing Plate to the wall Partially insert M4 screws into the outer two holes in each end of the b...

Page 3: ...ngs show connections inside the black terminal box on the outside of the heater and the inside of the CS 1 Controller Do NOT use power tools to undo or do up terminal screws Please Note Specified cable sizes are for typical installations correction factors may need to be used when determining actual cable sizes Standard Connection using CS 1 Controller Use 4mm 3 Core Mains Cable see note above Use...

Page 4: ...ned on after cleaning an unusual odour may be noted this is due to the dust particles which inevitably will be disturbed and will be burnt off from the heating element If in any doubt always consult a qualified electrician for advice 7 AUTO CUT OUT FUSE REPLACMENT This heater is fitted with a semi automatic safety device to prevent overheating The device will isolate the heating element while the ...

Reviews: