Development and production of systems for measurement and control

 2. Device description

Power quality analyzer PLA44 is designed for measurement and monitoring of electrical parameters in 2, 3 and 4

conductor networks and in TN and TT grids. PLA44 power quality analyzer architecture is based on fast 32 bits RISC
microprocessor  which  provides  high   computing   power   to   assure   the  device   being  fully  according  the   norm  IEC

61000-4-30 class A.

Parameter

L1 L2 L3 L4 L1-2 L2-3 L3-1 Σ

L1-L3

Σ

L1-L4

Max Min AVG Maxavg Measuring range Displaying range Accuracy

Phase voltage

10 ... 600 V

0 ... 1 MV

±0,1 %

Line voltage

18 ... 1000 V

0 ... 1 MV

±0,1 %

Frequency

40 ... 70 Hz

40 ... 70 Hz

10 mHz

Current

0,001 ... 6 A

0 ... 1 MA

±0,1 %

cosφ

0,01 L ... 0,01 C

0,01L ... 0,01C

±1 %

Power factor

0,01 L ... 0,01 C

0,01L ... 0,01C

±1 %

THDU L-N

0 ... 99,9 %

0 ... 99,9 %

±1 %

THDU L-L

0 ... 99,9 %

0 ... 99,9 %

±1 %

THDI

0 ... 99,9 %

0 ... 99,9 %

±1 %

Harmonics of voltage

0 ... 99,9 %

0 ... 99,9 %

Class 1

Group of interharmonics U

0 ... 99,9 %

0 ... 99,9 %

Class 1

Group of harmonics U

0 ... 99,9 %

0 ... 99,9 %

Class 1

Harmonics P

0 ... 99,9 %

0 ... 99,9 %

Class 1

Harmonics Q

0 ... 99,9 %

0 ... 99,9 %

Class 1

Harmonics I

0 ... 99,9 %

0 ... 99,9 %

Class 1

Group of interharmonics I

0 ... 99,9 %

0 ... 99,9 %

Class 1

Group of harmonics I

0 ... 99,9 %

0 ... 99,9 %

Class 1

Short-term flicker

0 ... 20,0 Pst

0 ... 20,0 Pst

Class A

Long-term flicker

0 ... 20,0 Plt

0 ... 20,0 Plt

Class A

Under-voltage

0 ... 100 %

0 ... 100 %

±0,2 %

Over-voltage

0 ... 100 %

0 ... 100 %

±0,2 %

Unbalance U

0 ... 100 %

0 ... 100 %

±0,15 %

Neutral point displacement

10 ... 600 V

0 ... 1 MV

±0,2 %

K-factor

Unbalance I

±0,5 %

Transients

25 μs

Events

10 ms

Ripple control signal

Active power

0 ... 10,8  kW

0 ... 999 GW

±0,4 %

Reactive power

0 ... 10,8  kvar

0 ... 999 Gvar

±0,4 %

Apparent power

0 ... 10,8  kVA

0 ... 999 GVA

±0,2 %

Distortion power

±0,5 %

Active /-

0 ... 999 GWh

0 ... 999 GVh

0,5S

Reactive ind. /-

0 ... 999 Gvarh

0 ... 999 Gvarh

Class 1

Reactive cap. /-

0 ... 999 Gvarh

0 ... 999 Gvarh

Class 1

Temperature

±1°C

* for ideal sinusoidal curve of voltage and current

Table 1: Measured and displayed parameters

 3. Installation

PLA44 is prepared for wall mounting in the fixed switch boards. In order to assure well ventilation, the PLA44  has to
be installed vertically. There has to be empty space at least 50 mm at the top and bottom and 20 mm at the sides.
PLA44 is fixed into switchboard wall by two clips that are placed on the device at the bottom and top.

BMR 

trading

Horní lán 17
779 00 Olomouc

Czech Republic

4

Tel: +420 778 066 566

[email protected]

www.bmr-trading.com

Summary of Contents for PLA44

Page 1: ...PLA 44 Power quality analyzer User and service manual version 1 4 BMR trading Horní lán 17 779 00 Olomouc Czech Republic 1 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 2: ...Voltage Change RVC 9 5 6 3 List of transients 9 5 6 4 Power cuts 9 6 Device settings 10 6 1 Language 10 6 2 Measurement 10 6 2 1 Network type 10 6 3 Analyser 12 6 3 1 Date and time 12 6 3 2 Reset 12 6 4 Communication 12 6 4 1 Ethernet 12 6 4 1 1 Web server 13 6 4 1 2 Modbus TCP 13 6 4 1 3 FTP server 13 6 4 2 RS485 13 6 4 3 Connection of PLA44 to LAN with NAT server 14 6 5 Events setting 15 6 6 Tra...

Page 3: ...meters 2 cursor key for moving up in menu and parameter change to higher value 3 cursor key for moving down in menu and parameter change to lower value 4 ESC key for canceling or return 5 Fn zoom key change function of other buttons BMR trading Horní lán 17 779 00 Olomouc Czech Republic 3 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 4: ...ss 1 Group of interharmonics I 0 99 9 0 99 9 Class 1 Group of harmonics I 0 99 9 0 99 9 Class 1 Short term flicker 0 20 0 Pst 0 20 0 Pst Class A Long term flicker 0 20 0 Plt 0 20 0 Plt Class A Under voltage 0 100 0 100 0 2 Over voltage 0 100 0 100 0 2 Unbalance U 0 100 0 100 0 15 Neutral point displacement 10 600 V 0 1 MV 0 2 K factor Unbalance I 0 5 Transients 25 μs Events 10 ms Ripple control si...

Page 5: ...cted via circuit breaker or switch and fuse 10 A which are placed close to the device Current measuring inputs have to be connected via current transformers either 5A or 1A ratio Picture 2 Full device connection at TN C network Notice If the voltage measuring inputs are connected over the voltage measuring transformers the power of measuring transformer power must be at appropriate level Voltage m...

Page 6: ...for activating the communication and data transfer 4 6 Temperature sensor Temperature sensor is connected directly to PLA44 inputs 20 and 21 according to the picture 2 The sensor is NTC type with resistance 10kΩ 25 C 4 7 Digital inputs outputs The instrument is equipped with two opto isolated transistor outputs inputs The outputs working mode is fully adjustable as an alarm output remotely control...

Page 7: ...provides values for short term flicker 10 minutes long term flicker 2 hours 5 2 Harmonics 5 3 Vectors 5 4 Bar graphs Voltage current and power values can be shown in bar graph form as well Bar graphs have synchronized automatic scale which is adjusted according to min and max displayed values to provide fast and clear comparison of measured values in all phases BMR trading Horní lán 17 779 00 Olom...

Page 8: ...form are displayed on the device screen and also web server if enabled 5 6 1 List of events Last 50 events of each type are captured in the nonvolatile memory with information about the start and end of the event and graph of the event On the device screen the event graph can be displayed with all detail information There are following type of events recorded in the PLA44 memory Type of event Desc...

Page 9: ...C event It is a dip or a swell 5 6 3 List of transients PLA44 captures transients of voltage as short as 25 μs and keeps last 50 transients of each type in the nonvolatile memory Type of event Description Different Transients started by differential threshold defined by zone Absolute Transients started by threshold absolute value defined by set value of voltage Waveform of transient event is possi...

Page 10: ...m frequency 50 Hz 45 75 Hz Udin Network nominal phase voltage 230 V 1V 750 kV Idin Network nominal phase current 5 A 1A 750 kA Voltage Tr Enable the usage of measuring voltage transformer No No Yes Current Tr Enable the usage of measuring current transformer No No Yes Utr Primary and secondary voltage of measuring voltage transformer 230V 230V 1 750 kV Itr Primary and secondary current of measurin...

Page 11: ...Development and production of systems for measurement and control BMR trading Horní lán 17 779 00 Olomouc Czech Republic 11 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 12: ...in software PMS For the finding the closest NTP server refer to the following link http support ntp org bin view Servers StratumOneTimeServers Parameter Description Factory settings Settings range Device time Date and UTC time in format for date YYYY MM DD and HH MM for time UTC time offset Time offset of the local time against to UTC Offset is set in seconds Daylight start Beginning of the summer...

Page 13: ...ting range Modbus TCP Enable or disable Modbus TCP feature Yes Yes No Modbus TCP port Defines the port on which the Modbus TCP is accessible 80 6 4 1 3 FTP server Parameter Description Factory setting Setting range FTP server Reference voltage level type Yes Yes No FTP port Port of the FTP service 21 FTP name User name for access to FTP server of PLA44 device admin FTP password Password for access...

Page 14: ... public IP address port 21 IP of PLA44 port 21 router public IP address port 50000 50005 IP of PLA44 port 50000 50005 Notice Number of port of 80 21 is possible change on router Range of ports 50000 50005 is fixed and it is not possible to change it On the PLA44 device it is necessary set following parameters in IP public FTP 21 factory value user name admin factory value password 1234 factory val...

Page 15: ...is limited by this maximum samples memory space 6 6 Transients setting Transient setting is defined by several parameters listed in table beneath Parameter Description Factory setting Setting range Pre Samples Number of recorded samples before the transient start 768 0 8000 Post Samples Number of recorded samples after the transient start 768 0 8000 Delay time Time delay before next transient reco...

Page 16: ...ment revenue meters and other devices Parameter Description Factory setting Setting range RVC threshold The RVC threshold is a percentage of Udin 3 3 1 100 RVC hysteresis The RVC hysteresis is a smaller percentage of Udin 1 1 20 Ripple control Adjustable by PMS 50 Hz 50 Hz 3 kHz According to the norm the ideal settings is RVC threshold on 3 5 of Udin and hysteresis on 1 of Udin 6 8 Information Inf...

Page 17: ...cessful firmware update connect the PLA44 via Ethernet to PC where the Update software will run Enter the IP address of the PLA44 and user name and password Pressing button Connect will verify accessibility of PLA44 and prepare connection for firmware update start Important While firmware is update device should be on the stable power supply and Ethernet connection should not be removed BMR tradin...

Page 18: ...ltage 24 VDC Maximum input consumption 10 mA Voltage transformer ratio 1 750 000 Current transformer ratio 1 750 000 Supply voltage power cuts memory 15 events Sampling rate 40 kHz Events trigger 10 ms Data memory for measured parameters 1 GB Display type and size VGA TFT 5 6 Temperature input NTC sensor 10 kΩ 25 C Communication port RS485 optional Modbus RTU 9 6 19 2 38 4 115 kBd Ethernet RJ45 10...

Reviews: