Installation
13
[ I ]
Installation
DANGER
Please see part General [G] for safety notes. Observe all notes with respect to safety and use of
the freeAir100.
2
nd
Room Connections
1.
Please select the correct connector for a device designed
for 2
nd
room connection:
• Connecting ducting, conduits and valves must have
low air stream resistance.
• For 2
nd
room connection the below stated decrease
in pressure must not be exceeded.
• The supply air conduits must not exceed
the below noted length.
Type of Conduit
Max. Air Flow for
2
nd
Room Exhaust
(= DIP switch setting)
Max. Pressure drop
2
nd
Room Exhaust
(at max. air flow)
=> Max. Length
(pressure drop for turns and
valves included)
1 x Flat-Flex 51 x 138 mm
30 m
3
/h
15 Pa
ca. 8 m
1 x Round-Flex
75 mm
30 m
3
/h
15 Pa
ca. 2.5 m
2 x Round-Flex
75 mm
60 m
3
/h
55 Pa
ca. 10 m
3 x Round-Flex
75 mm
100 m
3
/h
65 Pa
ca. 10 m
1 x Round
100 mm
100 m
3
/h
65 Pa
ca. 12 m