The heat exchanger consists of a steel shell insulated with 

closed-cell foam material, while the tube bundle is made 

with  copper  tubes.  The  heads  can  be  removed  for  tube 

inspection and cleaning. Victaulic couplings on water side 

(complete with nipple for connection). On the hydraulic 

connections  of  the  heat  exchanger,  there  are  also  pipe 

taps for the differential pressure switch, and wells for the 

temperature probes.

REFRIGERANT CIRCUIT

The refrigerant circuit of the unit comprises:

• 

discharge valve for each compressors

• 

charging valves

• 

liquid sight glass

• 

a solid cartridge dehydrator filter, which can be replaced 

on the fluid line;

• 

a hermetic dehydrator filter on the oil recovery line;

• 

an oil warning light;

•  electronic expansion valve
• 

pressure transducers for reading the high and low pres

-

sure  values  and  relevant  evaporating  and  condensing 

temperatures

• 

pressure transducers and a temperature probe designed 

to sense the subcooling value after the condenser;

• 

a high pressure switch;

• 

a high and low pressure safety valve;

•  an oil separator in the delivery line;
• 

an oil level warning light;

•  jet pumps for oil recovery from the evaporator.

The pipes of the refrigerant circuit and the heat exchanger 

on the user side are insulated with extruded closed-cell 

expanded elastomer.

With reference to the Hybrid Falling Film technology, the 

refrigerant subcooling value is checked through the meas

-

urement of the temperature and pressure downline of the 

condenser, as shown in the picture below:

The  electronic  expansion  valve  is  designed  to  offer  en

-

hanced stability during operation and to maximise the use 

of evaporation under all load conditions. This also acts as 

shut-off valve on the liquid line, thereby preventing haz

-

ardous refrigerant migrations during compressor stops.

ELECTRICAL CONTROL PANEL

The  electrical  control  panel  is  made  in  a  painted  galva

-

nised sheet-iron box with forced ventilation and IP21 pro

-

tection rating.
The electrical control panel of the basic unit comprises:

•  main disconnect switch
•  fuses to protect the compressors and the auxiliary cir-

cuits

•  compressor contactors
•  phase monitor
• 

potential-free general alarm contacts

• 

single potential free operating contacts

•  microprocessor controller with display accessible from 

the outside

• 

Capacitive backup battery for electronic expansion valve

• 

AC inverter fitted outside the panel

All the electrical cables inside the panel are numbered and 

the terminal board dedicated to the customer's connec-

tions is coloured blue so that it can be quickly identified 

in the panel.

Standard power supply of the unit is 400V/3~/50Hz

CONTROL BLUETHINK

Programmable microprocessor control, having proprietary 

control algorithms.
The control allows the following functions:

• 

Inverter management

• 

Vi management

• 

Electronic valve management

• 

water  temperature  adjustment,  with  outgoing  water 

control

• 

freeze protection

• 

compressor timings

• 

recording of the log of all machine inputs, outputs and 

states

• 

automatic rotation of compressor starting sequence

• 

recording of the alarm log

• 

management of capacity reduction of the compressors 

during starting, switching off and load tracking

• 

management of capacity reduction of the compressors 

in the event of operation outside the limits

Connection resources

The control includes the following connection resources:

• 

RS485 serial port with Modbus protocol

• 

Ethernet serial port with Modbus protocol; access to in

-

tegrated web server

• 

digital input for remote setting of state (on/off)

• 

digital input for setting of summer/winter mode (only 

for HPW version)

• 

digital input for selection of double set point

By default, the serial connections present as standard are 

enabled  only  for  reading  from  BMS.  Enabling  of  writing 

from BMS is to be requested when ordering.

Summary of Contents for Omega Sky Xi

Page 1: ...XLN super low noise version DC with total recovery Strengths Max efficiency at partial loads SEER up to 8 3 and SEPR up to 9 3 Ecodesign Tier 2 compliant Non flammable refrigerant R513A with GWP 573 H...

Page 2: ...17 Technical specifications 19 Ecodesign 23 Electrical specifications 29 Electrical specifications 30 Flow rate ranges of heat exchangers 31 Operating limits 32 Omega Sky Xi Omega Sky Xi OH Omega Sky...

Page 3: ...2...

Page 4: ...order to achieve the highest energy efficiency levels on the market with special reference to cooling applications The variation of the compression ratio caused by the sliding of the internal slide va...

Page 5: ...tops ELECTRICAL CONTROL PANEL The electrical control panel is made in a painted galva nised sheet iron box with forced ventilation and IP21 pro tection rating The electrical control panel of the basic...

Page 6: ...outlet of the user side heat ex changer that also acts as antifreeze probe thermal overload protection for compressors water differential pressure switch installed at the fac tory TESTING All the unit...

Page 7: ...tment on the compressor con sisting of a rigid outer cowling made of galvanised and painted sheet metal RAL 7035 lined with sound ab sorbing matting with high acoustic impedance material in between Co...

Page 8: ...he machine 2 way valve 3 way valve inverter controlled pump The signal is linked to the condensing pressure The signal is cumulative and therefore the accessory is suitable for combination on units in...

Page 9: ...y of a specific icon on the display of the controller This alarm stops the unit Accessory as an alternative to Refrigerant leak detector with automatic pump down Hydraulic circuit accessories CFC Flan...

Page 10: ...y monitored through the losses detected by the differential pressure transducer pe When the minimum allowed flow rate threshold is exceeded the control system will open the bypass valve Vbp to recircu...

Page 11: ...harge head of the primary circuit The operating principle can be summarized as follows Flowzer VPS performs intelligent control of the flow rate on the primary circuit and balances it compared to the...

Page 12: ...nd set point 2 to 12 C in heat pump mode only for HPW and OH units set point 1 at 45 C and set point 2 at 40 C CSP Set point compensation depending on external air temperature For units fitted with th...

Page 13: ...upply of the unit must compulsorily include neutral ENM Energy meter The accessory allows the main electrical quantities including voltage current power to be read on the three phases via current tran...

Page 14: ...e reversal an alarm is generated that stops the machine to prevent damage to its main parts FARE Fast Restart The Fast Restart accessory enables the controller to carry out a fast restart of the unit...

Page 15: ...units peripherals Subscribing to any of the Blueye Cloud enables viewing the history of the monitored variables in the form of both numerical values and graphs downloading the history of variables in...

Page 16: ...simple serial cable so allowing their operat ing logics to be merged into a single consciousness that pursues the maximum energy efficiency of the system The RS485 serial interface is already included...

Page 17: ...torily be one of the free cooling units The Multilogic function that can be requested with the unit can be FM0 Multilogic function for Slave unit FM2 Multilogic function for Master unit for managing u...

Page 18: ...allation by the customer and replaces the water differential pressure switch standard GABB Packaging in wooden crate The unit is protected by a made to measure wooden crate The accessory is mandatory...

Page 19: ...er The accessory provides for the installation of a wooden sled for loading and a fixing system inside the container by a strap If this accessory is requested loading is only possible on containers an...

Page 20: ...97 99 101 Sound pressure levels LN 5 dB A 76 76 77 77 78 77 78 78 80 82 Sound power levels XLN 4 dB A 91 91 92 92 93 93 94 94 96 98 Sound pressure levels XLN 5 dB A 73 73 74 74 75 74 75 75 77 79 Dimen...

Page 21: ...1500 1550 1550 1550 1550 1550 1670 1670 Height mm 2050 2050 2100 2100 2100 2150 2150 2300 2400 Operating weight kg 2215 2335 2694 2832 2987 3381 3509 4260 4742 1 Source side heat exchanger inlet outl...

Page 22: ...4742 1 Source side heat exchanger inlet outlet water temperature 30 35 C user side heat exchanger inlet outlet water temperature 12 7 C Values com pliant with standard EN 14511 2 Source side heat exch...

Page 23: ...1 101 102 102 104 Sound pressure lev 5 dB A 81 81 82 82 83 82 83 83 85 Sound power levels LN 4 dB A 94 94 95 95 96 96 97 97 99 Sound pressure levels LN 5 dB A 76 76 77 77 78 77 78 78 80 Sound power le...

Page 24: ...atically illustrates the correspondence between product and reference energy ratio Some notes and clarifications For comfort applications regulation 2016 2281 sets the sc SEER ratio in two different o...

Page 25: ...icated below REGULATION 2016 2281 comfort application REGULATION 2016 2281 process application REGULATION 2013 813 The conformity of the product must be checked according to the type of application wh...

Page 26: ...exemption from Ecodesign PROCESS APPLICATION PRODUCT OUTLET WATER TEMPERA TURE COMPLIANCE INDEX REGULATION Chiller 2 C 12 C SEPR 2016 2281 12 C 8 C 2 C exemption from Ecodesign Some specifications an...

Page 27: ...applications SEPR for process applications As regards the 2016 2281 regulation starting from 1 January 2021 the minimum required efficiency limit will be raised Tier 2 compared to the current standard...

Page 28: ...1 User side heat exchanger water inlet outlet temperature 12 7 C low temperature application with reference to regulation 2016 2281 and stand ard EN 14825 3 User side heat exchanger water inlet outle...

Page 29: ...ature 47 55 C SCOP MT Average climate profile with reference to regulation 2013 813 and norm EN 14825 OMEGA SKY Xi OH 25 1 29 1 35 1 R513A REGULATION 2013 813 Pdesign 1 kW 271 322 384 Compliance 1 Y Y...

Page 30: ...a qualified technician based on the length of the line the type of cable used and the type of installation OMEGA SKY Xi 53 1 60 1 72 1 81 1 97 1 General electrical specifications Max absorbed power F...

Page 31: ...on must be determined by a qualified technician based on the length of the line the type of cable used and the type of installation OMEGA SKY Xi HPW OH 53 1 60 1 72 1 81 1 General electrical specifica...

Page 32: ...19 81 1 70 209 83 248 97 1 81 243 96 288 OMEGA SKY Xi HPW R513A Evaporator Condenser Qmin Qmax Qmin Qmax m h m h m h m h 25 1 30 90 24 71 29 1 36 108 28 84 35 1 43 129 33 99 40 1 49 146 37 111 47 1 55...

Page 33: ...nt ice formation in the exchanger The inlet and outlet temperatures of the user side exchanger must be given on ordering to allow correct setting of the alarm parame ters and verification of the sizin...

Page 34: ...60 101 82 The acoustic data are related to standard conditions source on a reflective surface in free field in referable and reproducible oper ating conditions The environment and the installation co...

Page 35: ...ses or for the verification of binding limits Reference conditions source side heat exchanger input output water temperature 30 35 C user side heat exchanger input output water temperature 12 7 C unit...

Page 36: ...5 DIMENSIONAL DIAGRAMS OMEGA SKY XI XI OH XI HPW DDIM000472 Note These drawings are not contractually binding For the installation design refer to the specific dimensional drawing available on request...

Page 37: ...0 4 pH 7 5 8 5 Electrical conductivity 10 500 S cm Organic elements Hydrogen carbonate HCO3 70 300 ppm Sulphates SO4 2 50 ppm Hydrogen carbonate Sulphates HCO3 SO4 2 1 Chlorides Cl 50 ppm Nitrates NO3...

Page 38: ...ors less wear of them and an increase in the efficiency of the system as a consequence of a reduc tion in the number of transients where Vmin is the minimum water content of the system l Ptot is the t...

Page 39: ...l units side by side you should consider the position and dimensions of the manifolds of the heat exchangers Once the best position for the unit has been identified you must check that the support sla...

Page 40: ...39...

Page 41: ...TC_0000_OSXi_EN_Rev00_20190109...

Reviews: