OMEGA SKY XI

Omega Sky Xi is a water-condensed liquid chiller for in

-

door applications, available in heat pump version also.

This  range  features  a  semi-hermetic,  inverter-controlled 

screw compressor to obtain max. performances at partial 

loads, a latest generation Hybrid Falling Film evaporator 

with  low  refrigerant  load,  and  a  flooded  shell  and  tube 

condenser.

These  elements  make  Omega  Sky  Xi  an  extremely  per

-

forming machine in all operating conditions, which enables 

it to largely exceed the targets mandated by the existing 

regulations and to ensure max. comfort levels.

REFRIGERANT

Refrigerant R513A standard.
R513A is distinguished by its low environmental impact, 

with GWP=573 (*). It is also a non-toxic and non-flam

-

mable fluid: A1 classification in accordance with ASHRAE; 

PED 2.
These characteristics make R513A ideal for indoor units; 

they also facilitate adoption of the model in places where 

there  are  certain  local  requirements  regarding  the  envi

-

ronmental impact caused by refrigerants. 
This has positive effects on transport, operation and main

-

tenance and also on overall cost effectiveness, as regards 

possible taxation or restrictions on the use of refrigerants 

with high environmental impact.
The model can be supplied with refrigerant R134a as op

-

tion.

(*) GWP (AR5), pursuant to IPCC V, evaluated over a span 

of 100 years.

STRUCTURE

Consists  of  polyester  powder  coated  hot  dip  galvanised 

sheet steel profiles (RAL 9005).
The  electrical  control  panel  is  made  in  a  polyester  pow

-

der-coated hot dip galvanised sheet steel box (RAL 7035).

COMPRESSORS

Units  fit  innovative  screw  compressors  with  a  variable 

compression ratio, which ensure optimised operation un-

der all operating conditions.
The BlueThink controller constantly monitors the evaporat

-

ing and condensing temperatures of the unit and changes 

the compression ratio of the compressors to obtain the 

max. achievable efficiency.
The compressors in use are designed according to an ex

-

clusive BlueBox specification in order to achieve max. effi

-

ciency both under partial and full load conditions.
Continuous reduction of the output capacity is implement-

ed with a regulation from 25% to 100% in order to achieve 

the  highest  energy  efficiency  levels  on  the  market,  with 

special reference to cooling applications. The variation of 

the compression ratio caused by the sliding of the internal 

slide valve, in combination with capacity reduction of the 

refrigeration demand by the inverter, allows for the maxi

-

misation of the energy efficiency of the unit in all operat

-

ing conditions.

In  addition  to  managing  capacity  modulation,  BlueThink 

also controls all safety devices so that the compressor can 

operate within its operating limits at all times and simulta

-

neously safeguard its operation and reliability. Compressor 

lubrication is ensured by the pressure difference between 

the delivery and the suction lines, thanks to the regulation 

action performed by BlueThink.
All the compressors are fitted with check valve on delivery 

side, metal mesh filter on suction side and electronic pro

-

tection with temperature sensors directly inserted in the 

windings and on the delivery pipe.
Startup in compressors featuring an inverter is of the “Di

-

rect On Line” type with an inverter-controlled acceleration 

ramp that minimises inrush currents.

In  addition  to  the  obvious  energy  savings  arising  from 

greater efficiency, the use of a full inverter unit also brings 

advantages in terms of installation:

• 

For these units, the cosφ (power factor) is always great

-

er  than  0.95,  therefore  making  external  power  factor 

correction systems unnecessary.

• 

The maximum inrush current of the unit is always lower 

than its maximum absorbed current (calculated in the 

worst operating condition), therefore making the power 

cables and line protection devices less onerous.

All the compressors are fitted as standard with crankcase 

heater and discharge valve.

SOURCE-SIDE HEAT EXCHANGER

Flooded shell-and-tube heat exchanger, with single water 

passage on tube side. Steel shell, and tube bundle made 

with  copper  tubes.  The  heads  can  be  removed  for  tube 

inspection and cleaning. Victaulic couplings on water side 

(complete with nipple for connection).

USER-SIDE HEAT EXCHANGER

Latest  generation  shell  and  tube  heat  exchanger  Hybrid 

Falling Film with two passes.
The new technology combines the features of a traditional 

flooded evaporator and the Falling Film evaporator, thus 

ensuring low approach temperatures and a low refrigerant 

load.
Below is a sample cross-section of the evaporator.

Summary of Contents for Omega Sky Xi

Page 1: ...XLN super low noise version DC with total recovery Strengths Max efficiency at partial loads SEER up to 8 3 and SEPR up to 9 3 Ecodesign Tier 2 compliant Non flammable refrigerant R513A with GWP 573 H...

Page 2: ...17 Technical specifications 19 Ecodesign 23 Electrical specifications 29 Electrical specifications 30 Flow rate ranges of heat exchangers 31 Operating limits 32 Omega Sky Xi Omega Sky Xi OH Omega Sky...

Page 3: ...2...

Page 4: ...order to achieve the highest energy efficiency levels on the market with special reference to cooling applications The variation of the compression ratio caused by the sliding of the internal slide va...

Page 5: ...tops ELECTRICAL CONTROL PANEL The electrical control panel is made in a painted galva nised sheet iron box with forced ventilation and IP21 pro tection rating The electrical control panel of the basic...

Page 6: ...outlet of the user side heat ex changer that also acts as antifreeze probe thermal overload protection for compressors water differential pressure switch installed at the fac tory TESTING All the unit...

Page 7: ...tment on the compressor con sisting of a rigid outer cowling made of galvanised and painted sheet metal RAL 7035 lined with sound ab sorbing matting with high acoustic impedance material in between Co...

Page 8: ...he machine 2 way valve 3 way valve inverter controlled pump The signal is linked to the condensing pressure The signal is cumulative and therefore the accessory is suitable for combination on units in...

Page 9: ...y of a specific icon on the display of the controller This alarm stops the unit Accessory as an alternative to Refrigerant leak detector with automatic pump down Hydraulic circuit accessories CFC Flan...

Page 10: ...y monitored through the losses detected by the differential pressure transducer pe When the minimum allowed flow rate threshold is exceeded the control system will open the bypass valve Vbp to recircu...

Page 11: ...harge head of the primary circuit The operating principle can be summarized as follows Flowzer VPS performs intelligent control of the flow rate on the primary circuit and balances it compared to the...

Page 12: ...nd set point 2 to 12 C in heat pump mode only for HPW and OH units set point 1 at 45 C and set point 2 at 40 C CSP Set point compensation depending on external air temperature For units fitted with th...

Page 13: ...upply of the unit must compulsorily include neutral ENM Energy meter The accessory allows the main electrical quantities including voltage current power to be read on the three phases via current tran...

Page 14: ...e reversal an alarm is generated that stops the machine to prevent damage to its main parts FARE Fast Restart The Fast Restart accessory enables the controller to carry out a fast restart of the unit...

Page 15: ...units peripherals Subscribing to any of the Blueye Cloud enables viewing the history of the monitored variables in the form of both numerical values and graphs downloading the history of variables in...

Page 16: ...simple serial cable so allowing their operat ing logics to be merged into a single consciousness that pursues the maximum energy efficiency of the system The RS485 serial interface is already included...

Page 17: ...torily be one of the free cooling units The Multilogic function that can be requested with the unit can be FM0 Multilogic function for Slave unit FM2 Multilogic function for Master unit for managing u...

Page 18: ...allation by the customer and replaces the water differential pressure switch standard GABB Packaging in wooden crate The unit is protected by a made to measure wooden crate The accessory is mandatory...

Page 19: ...er The accessory provides for the installation of a wooden sled for loading and a fixing system inside the container by a strap If this accessory is requested loading is only possible on containers an...

Page 20: ...97 99 101 Sound pressure levels LN 5 dB A 76 76 77 77 78 77 78 78 80 82 Sound power levels XLN 4 dB A 91 91 92 92 93 93 94 94 96 98 Sound pressure levels XLN 5 dB A 73 73 74 74 75 74 75 75 77 79 Dimen...

Page 21: ...1500 1550 1550 1550 1550 1550 1670 1670 Height mm 2050 2050 2100 2100 2100 2150 2150 2300 2400 Operating weight kg 2215 2335 2694 2832 2987 3381 3509 4260 4742 1 Source side heat exchanger inlet outl...

Page 22: ...4742 1 Source side heat exchanger inlet outlet water temperature 30 35 C user side heat exchanger inlet outlet water temperature 12 7 C Values com pliant with standard EN 14511 2 Source side heat exch...

Page 23: ...1 101 102 102 104 Sound pressure lev 5 dB A 81 81 82 82 83 82 83 83 85 Sound power levels LN 4 dB A 94 94 95 95 96 96 97 97 99 Sound pressure levels LN 5 dB A 76 76 77 77 78 77 78 78 80 Sound power le...

Page 24: ...atically illustrates the correspondence between product and reference energy ratio Some notes and clarifications For comfort applications regulation 2016 2281 sets the sc SEER ratio in two different o...

Page 25: ...icated below REGULATION 2016 2281 comfort application REGULATION 2016 2281 process application REGULATION 2013 813 The conformity of the product must be checked according to the type of application wh...

Page 26: ...exemption from Ecodesign PROCESS APPLICATION PRODUCT OUTLET WATER TEMPERA TURE COMPLIANCE INDEX REGULATION Chiller 2 C 12 C SEPR 2016 2281 12 C 8 C 2 C exemption from Ecodesign Some specifications an...

Page 27: ...applications SEPR for process applications As regards the 2016 2281 regulation starting from 1 January 2021 the minimum required efficiency limit will be raised Tier 2 compared to the current standard...

Page 28: ...1 User side heat exchanger water inlet outlet temperature 12 7 C low temperature application with reference to regulation 2016 2281 and stand ard EN 14825 3 User side heat exchanger water inlet outle...

Page 29: ...ature 47 55 C SCOP MT Average climate profile with reference to regulation 2013 813 and norm EN 14825 OMEGA SKY Xi OH 25 1 29 1 35 1 R513A REGULATION 2013 813 Pdesign 1 kW 271 322 384 Compliance 1 Y Y...

Page 30: ...a qualified technician based on the length of the line the type of cable used and the type of installation OMEGA SKY Xi 53 1 60 1 72 1 81 1 97 1 General electrical specifications Max absorbed power F...

Page 31: ...on must be determined by a qualified technician based on the length of the line the type of cable used and the type of installation OMEGA SKY Xi HPW OH 53 1 60 1 72 1 81 1 General electrical specifica...

Page 32: ...19 81 1 70 209 83 248 97 1 81 243 96 288 OMEGA SKY Xi HPW R513A Evaporator Condenser Qmin Qmax Qmin Qmax m h m h m h m h 25 1 30 90 24 71 29 1 36 108 28 84 35 1 43 129 33 99 40 1 49 146 37 111 47 1 55...

Page 33: ...nt ice formation in the exchanger The inlet and outlet temperatures of the user side exchanger must be given on ordering to allow correct setting of the alarm parame ters and verification of the sizin...

Page 34: ...60 101 82 The acoustic data are related to standard conditions source on a reflective surface in free field in referable and reproducible oper ating conditions The environment and the installation co...

Page 35: ...ses or for the verification of binding limits Reference conditions source side heat exchanger input output water temperature 30 35 C user side heat exchanger input output water temperature 12 7 C unit...

Page 36: ...5 DIMENSIONAL DIAGRAMS OMEGA SKY XI XI OH XI HPW DDIM000472 Note These drawings are not contractually binding For the installation design refer to the specific dimensional drawing available on request...

Page 37: ...0 4 pH 7 5 8 5 Electrical conductivity 10 500 S cm Organic elements Hydrogen carbonate HCO3 70 300 ppm Sulphates SO4 2 50 ppm Hydrogen carbonate Sulphates HCO3 SO4 2 1 Chlorides Cl 50 ppm Nitrates NO3...

Page 38: ...ors less wear of them and an increase in the efficiency of the system as a consequence of a reduc tion in the number of transients where Vmin is the minimum water content of the system l Ptot is the t...

Page 39: ...l units side by side you should consider the position and dimensions of the manifolds of the heat exchangers Once the best position for the unit has been identified you must check that the support sla...

Page 40: ...39...

Page 41: ...TC_0000_OSXi_EN_Rev00_20190109...

Reviews: