Press and Hold to configure:
Ÿ
Remote Start / Stop
Ÿ
TFD (Tube Failure Detection) sensitivity
Ÿ
FVS (Flow Verification Sensor) time delay - requires sensor
Ÿ
4-20 mA output, available on certain models
Mode 0
Mode 1 - Manual
Run pump locally by selecting pump speed (1 - 100%).
Ÿ
Control speed by using up or down arrows after start button is
pressed.
Ÿ
Control speed by entering Mode 1 setup and selecting desired
pump speed (1 - 100%)
Mode 2 - 4-20 mA Input Signal
Run pump remotely via external 4-20 mA signal.
Ÿ
Press and Hold “Select Run Mode” button with Mode 2
selected to configure settings.
Ÿ
Select Mode 2 and press START button to allow pump to be
controlled by external 4-20mA signal.
Mode 3 - Frequency (Hz) Input Signal
Run pump remotely via external high frequency (Hz) signal.
Ÿ
Press and Hold “Select Run Mode” button with Mode 3
selected to configure settings.
Ÿ
Select Mode 3 and press START button to allow pump to be
controlled by external frequency (Hz) signal.
Mode 4 - Pulse Batch Input Signal
(low speed pulse)
Run pump remotely via external low speed pulse signal.
Ÿ
Press and Hold “Select Run Mode” button with Mode 4
selected to configure settings.
Ÿ
Select Mode 4 and press START button to allow pump to be
controlled by external low speed pulse signal.
SEt
0
Mode 1
OFF
1
Mode 2
OFF
2
Mode 3
OFF
3
Mode 4
OFF
4
SPEED
mA
Hz
Hz
ON
6.3
Mode Descriptions
Press and release
To select Run Mode
Mode 1: Manual
Mode 2: 4-20mA input
Mode 3: Frequency input
Mode 4: Pulse / Batch
Press and Hold
To configure selected Mode
Mode 0: Setup
Mode 1: Manual
Mode 2: 4-20mA input
Mode 3: Frequency input
Mode 4: Pulse / Batch
Press and release
To prime pump (60 seconds)
Press and hold
To change rotor direction
clockwise or counterclockwise
Important:
Hold button down to
trigger rotor reversal
Press and release
To scroll through menu options
in Setup mode.
To increase value while in
programming mode.
Press UP arrow to increase
pump speed (output) in Manual
mode (Mode 1).
Press and release
To Start pump.
To begin listening (reacting) to
external signals.
Press and release
To Stop pump.
Press and release
To scroll through menu options
in Setup mode.
To scroll through pump speed
(output) and current incoming
signals in run modes:
Mode 2, Mode 3, & Mode 4
Press and release
To scroll through menu options
in Setup mode.
To decrease value while in
programming mode.
Press DOWN arrow to
decrease pump speed (output)
in Manual mode (Mode 1).
To view amount of run time hours on currently installed tube.
START + DOWN arrow displays current pump tube timer.
Hold down START button, then press and release DOWN arrow.
Tube Life Timer
6.2
A2V Touch Pad Layout
®
Page 15
Page 14
®
FLEXFLO A2
®
FLEXFLO A2