background image

4-20 mA Input

mA

Displays current incoming signal

12.5

Å

É

ÄÈ

Displays motor run status

When in the run mode, 
you can view the current 

 

pump output speed and 
input signal values by 
pressing 

RIGHT 

the 

arrow. 

Tip!

Example 1

0

2

4

6

8

10

0

25

50

75

100

Pump

Motor Speed (%)

VDC Input

from external source

0 VDC = 0% Pump Output

10 VDC = 100% Pump Output

Example 2

0

25

50

75

100

0 VDC = 100% Pump Output

10 VDC = 0% Pump Output

Example 3

0

25

50

75

100

0 VDC = 20% Pump Output

8 VDC = 45.3% Pump Output

0%

Output

Pump

Motor Speed (%)

Pump

Motor Speed (%)

100%

Output

100%

Output

0%

Output

45.3%

Output

0

2

4

6

8

10

VDC Input

from external source

0

2

4

6

8

10

VDC Input

from external source

20%

Output

- 0-10 VDC Input

- 0-10 VDC Input

Min VDC Signal:

Input Min. VDC

0.00

0

- 0-10 VDC Input

- 0-10 VDC Input

Max VDC Signal:

Input Max. VDC signal

0.00

1

Press ENTER to set.

Press ENTER to set.

Flow @ Min Signal:

00.0

0

Flow @ Max Signal:

00.0

0

Input Flow Rate
                          

RPM

Input Flow Rate
                          

RPM

4.3.3  

0 - 10 VDC Input (Volt DC)

Used to remotely control the pump with an incoming 0-10 VDC signal.

Default settings:  

0 VDC = 0% motor speed

 

 

 

 

 

10 VDC = 100% motor speed

Press MODE button until 

0 - 10 VDC Input i

s displayed in the top line of the 

display. 

To configure the pump, navigate to 

0 - 10 VDC Input

 menu by using the short-

cut method described at the beginning of the  section, or by pressing MENU 
button, then selecting Input Setup, Input Modes, and then 

0 - 10 VDC Input

.

Four points on the slope must be defined; 1) a low VDC value, 2) an output rate 
at the low VDC value, 3) a high VDC value, and 4) an output rate at the high 
VDC value. 

To input VDC values, press the RIGHT ARROW to select the digit to change, 
press UP or DOWN arrow to scroll through 0 - 9 on selected digit. Press enter to 
save changes and move to the next input screen.

To input flow rate values, press the RIGHT ARROW to select the user defined 
flow rate unit of measure, motor RPM, or %Speed values. Press UP or DOWN 
arrow to increase or decrease the value. Press and hold the arrow to increase or 
decrease progressively faster. Press enter to save changes and move to the 
next input screen.

Continue this process until all four screens have been configured.

If you used the short-cut to enter 0 - 10 VDC Input setup, press and hold Mode button until Run Mode screen is 
displayed.

If you used the Menu button to navigate to 0 - 10 VDC Input setup, you must navigate back out of menu structure. 
To do this you must select <-Esc at bottom of every screen menu until you see Run Mode screen displayed.

0

200 400 600 800 1000

0

25

50

75

100

Pump

Motor Speed (%)

Frequency Input (Hz)

0 Hz = 0% Pump Output

1000 Hz = 100% Pump Output

0

25

50

75

100

0 Hz = 100% Pump Output

1000 Hz = 0% Pump Output

0

25

50

75

100

0 Hz = 20% Pump Output

800 Hz = 50% Pump Output

0%

Output

Pump

Motor Speed (%)

Pump

Motor Speed (%)

100%

Output

100%

Output

0%

Output

50%

Output

0

200 400 600 800 1000

0

200 400 600 800 1000

20%

Output

Frequency Input (Hz)

Frequency Input (Hz)

Examples:

4.3.4  

Frequency Input (Hz)

Used to remotely control the pump with an incoming high speed frequency 
signal. Typically used with flow meters or other external devices.

Default settings:  

0 Frequency (Hz) = 0% motor speed

 

 

 

 

 

1000 Frequency (Hz) = 100% motor speed

Press MODE button until 

Frequency Input  

is displayed in the top line of the 

display. 

To configure the pump, navigate to 

Frequency Input

 menu by using the short-

cut method described at the beginning of section, or by pressing MENU button, 
then selecting Input Setup, Input Modes, and then 

Frequency Input

.

Four points on the slope must be defined; 1) a low Hz value, 2) an output rate at 
the low Hz value, 3) a high Hz value, and 4) an output rate at the high Hz value. 

To input Hz values, press the RIGHT ARROW to select the digit to change, 
press UP or DOWN arrow to scroll through 0 - 9 on selected digit. Press enter to 
save changes and move to the next input screen.

To input flow rate values, press the RIGHT ARROW to select the user defined 
flow rate unit of measure, motor RPM, or %Speed values. Press UP or DOWN 
arrow to increase or decrease the value. Press and hold the arrow to increase or 
decrease progressively faster. Press enter to save changes and move to the 
next input screen.

Continue this process until all four screens have been configured.

If you used the short-cut to enter Frequency Input setup, press and hold Mode button until Run Mode screen is 
displayed.

If you used the Menu button to navigate to Frequency Input setup, you must navigate back out of menu structure. 
To do this you must select <-Esc at bottom of every screen menu until you see Run Mode screen displayed.

- Frequency Input

- Frequency Input

Min Freq. Signal:

Input Min. Freq. (Hz)

000

0

- Frequency Input

- Frequency Input

Max Freq. Signal:

Max. Freq. (Hz) signal

000

1

Press ENTER to set.

Press ENTER to set.

Flow @ Min Signal:

00.0

0

Flow @ Max Signal:

00.0

0

Input Flow Rate
                          

GPH

Input Flow Rate 
                         

GPH

300

Frequency Input

Hz 

Displays current incoming signal

Å

É

ÄÈ

When in the run mode, 
you can view the current 
pump output speed and 
input signal values by 
pressing 

RIGHT 

the 

arrow. 

Tip!

Displays motor run status

Page 18

Page 19

®

CHEM-FEED  MD3

®

CHEM-FEED  MD3

Summary of Contents for CHEM-FEED MD3 Series

Page 1: ...Diaphragm Metering Pump Series MD3 CHEM FEED...

Page 2: ...3 1 Manual Adjust manual speed adjust 16 4 3 2 4 20 mA Input 17 4 3 3 0 10 VDC Input 18 4 3 4 Frequency Input Hz 19 4 3 5 Pulse Batch low speed batch 20 4 3 6 Manual Cycle Adjust repeating cycle time...

Page 3: ...m Model Number Matrix READ THE INSTRUCTION MANUAL PRIOR TO INSTALLATION AND USE 1 714 893 8529 sales blue white com customerservice blue white com 5300 Business Drive Huntington Beach CA 92649 Page 3...

Page 4: ...115V60Hz NEMA 5 15 USA 230V60Hz NEMA 6 15 USA 220V50Hz CEE 7 VII EU 240V50Hz AS 3112 Australia New Zealand Pump Head Assembly Pump Head PVDF Manifold PVDF Adapter Connections PVDF Valve Cartridges PVD...

Page 5: ...ite s output Flow Verification Sensor FVS system Includes stainless steel extended mounting brackets Lifts pump 4 1 2 11 43 cm for easy access in hard to reach areas Enclosure Rating NEMA 4X Construct...

Page 6: ...n check valve at discharge side of pump to prevent system fluid from flowing back through pump during pump maintenance A pressure relief valve is recommended at discharge of pump Bolt pump to a stable...

Page 7: ...0cm 4 00in 10 15cm n Made out of tough Stainless Steel n Provides a stable mounting surface Stainless Steel extended brackets allow the pump to be securely mounted to most any surface floor shelf or s...

Page 8: ...d and sealed Never strap control input output cables and power cables together Power Interruption This pump has a user programmable auto restart feature which will either restore the pump to the opera...

Page 9: ...AMP MAX AT 125 VOLT AC 0 8 AMP MAX AT 30 VOLT DC 5A SLOW BLOW 20 X 5MM 1 2 3 T1 PULSE GND 4 20 1 2 3 T1 PULSE GND 4 20 0 10 15VDC 1 2 T2 0 1000 HZ MAX NEGATIVE POSITIVE POSITIVE NEGATIVE NO VOLTAGE 96...

Page 10: ...elect menu items increase menu values by one and increase pump output in Manual Speed Adjust mode Press and hold to increase values progressively faster Press and release to stop the pump Press and re...

Page 11: ...e While making a selection where only one choice is allowed you will see a radio button Radio button example In a screen where you are making changes you will see the word Done located at the bottom o...

Page 12: ...e menu structure and enter the run mode Configuration Display Language Set Password Display Rate Esc Reset to Default Display Language English Spanish German Done French Display Language Configuration...

Page 13: ...gled through Speed RPM and your selected Display Rate by pressing the right arrow button Press MENU button to enter the menu structure Select Configuration and Press ENTER button Select Display Rate a...

Page 14: ...wrate Flowrate ML min Press ENTER to set 0000 0 1 Contact Input Close Stop Pump Open Stop Pump Input Time Delay OFF 000 Range 1 255 sec Disable 00 0 Input Setup 4 20 mA Input Frequency Input Pulse Inp...

Page 15: ...rate Input Modes Contact Input Set FVS Esc Hidden Remote Local Set DFD Set Rev Alarm Max Flowrate Input Max Flowrate Flowrate ML min Press ENTER to set 0000 0 1 To calculate the Max Flowrate To determ...

Page 16: ...ack out of the menu structure To do this you must select Esc at the bottom of every screen menu until you see the Run Mode screen displayed Tip The Manual Speed Adjust mode can be combined with Contac...

Page 17: ...process until all four screens have been configured If you used short cut to enter 4 20 mA input setup press and hold the Mode button until the Run Mode screen is displayed If you used Menu button to...

Page 18: ...top line of the display To configure the pump navigate to 0 10 VDC Input menu by using the short cut method described at the beginning of the section or by pressing MENU button then selecting Input Se...

Page 19: ...select the digit to change press UP or DOWN arrow to scroll through 0 9 on selected digit Press enter to save changes and move to the next input screen To input flow rate values press the RIGHT ARROW...

Page 20: ...k by continuously pressing the RIGHT button Press ENTER to save the changes Continue this process until all three screens have been configured If you used the short cut to enter Pulse Batch setup then...

Page 21: ...onfigured If you used the short cut to enter Manual Cycle Adjustment setup press and hold Mode button until Run Mode screen is displayed If you used the Menu button to navigate to Cycle Adjustment set...

Page 22: ...xt digit to the right If you pass your desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process until two screens have been...

Page 23: ...arrow to scroll over to next digit to the right If you pass your desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process un...

Page 24: ...esired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process until all four screens have been configured If you used the short cu...

Page 25: ...gering due to flickering high speed electrical switches a trigger delay time can be configured to delay the pump command The delay time unit of measure is seconds A two second delay time is recommende...

Page 26: ...n discharge side of MD3 pump Wiring for sensor can be connected directly to a MD3 pump Pump will stop pumping if sensor detects no flow A relay will then close allowing for remote alarm indication or...

Page 27: ...an 430 microsiemens will not be detected This system is capable of detecting presence of a large number of chemicals including Sodium Hypochlorite Chlorine Hydrochloric muriatic Acid Sodium Hydroxide...

Page 28: ...etting section 4 4 is switched to disabled while LOCAL ONLY is selected This menu setting will return to the previous setting when REMOTE ONLY or DISABLED is selected Input Setup Input Modes Contact I...

Page 29: ...Stop Frequency Mode Cycle Timer Mode Dispensing Mode Manual Dosing Prop Dosing 0 10 VDC Mode Pulse Mode Disable FVS DFD Pump Run Stop 4 20mA Mode Manual Mode Frequency Mode Cycle Timer Mode Dispensing...

Page 30: ...0 Pump Output 4 mA 100 Pump Output 20 mA Signal Output Frequency Output Disable Done 4 20 mA Output Default 4 20 mA output settings shown Signal Output Disable Done 4 20 mA Output Default Frequency H...

Page 31: ...r does not assume responsibility for damage to pump that has been caused by chemical attack 6 2 Cleaning Pump Pump will require occasional cleaning especially Injection fitting Footvalve Strainer and...

Page 32: ...7 0 Exploded view and parts list 1 2 4 6 8 7 10 22 9 15 14 3 13 11 3 12 Page 32 CHEM FEED MD3...

Page 33: ...001 505 MANIFOLD WITH FLANGE AND UNION NUT PLUG WITH O RING EP 6 90002 350 DRIVE HEAD INSERT 2 7 72000 583 KIT DIAPHRAGM PVDF MD3 2 8 70001 345 CARTRIDGE VALVE TFE P 8 70001 346 CARTRIDGE VALVE EP 9 9...

Page 34: ...32 151 303 751 1508 2252 3041 RPM 1 3 10 19 48 95 142 190 GPH 0 5 2 4 4 8 11 9 23 9 35 7 48 2 Feed Rate at 90 PSIg ML MIN 25 145 278 694 1388 2107 2391 RPM 1 3 10 19 48 95 142 190 GPH 0 4 2 3 4 4 11 0...

Page 35: ...Page intentionally left blank Page 35 CHEM FEED MD3...

Page 36: ...Page intentionally left blank Page 36 CHEM FEED MD3...

Page 37: ...Page intentionally left blank Page 37 CHEM FEED MD3...

Page 38: ...iption of the problem and proof of purchase Prepay all shipping and insurance cost COD shipments will not be accepted Damage caused by improper packaging is the responsibility of the sender When In Wa...

Page 39: ...ia New Zealand 9 230V 50HZ power cord BS 1363 A plug United Kingdom X No Power Cord Elastomer Material O Rings V TFE P E EP Miscellaneous Options leave blank for standard model A Hastelloy C check val...

Page 40: ...ramework available to them for the return recycle recovery of WEEE and minimize any potential effects of EEE on the environment and human health due to the presence of hazardous substances The WEEE ma...

Reviews: