Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 0 - 4,500 ft
Number of 90° Elbows
Used
2" Pipe
2" Pipe
2" Pipe
Capacity
Capacity
Capacity
70
90
110
70
90
110
70
90
110
1
53
37
17
100
84
49
116
109
109
2
48
32
12
95
79
44
111
104
104
3
43
27
7
90
74
39
106
99
99
4
38
22
n/a
85
69
34
101
94
94
5
33
17
80
64
29
96
89
89
6
28
12
75
59
24
91
84
84
7
23
7
70
54
19
86
79
79
8
18
n/a
65
49
14
81
74
74
9
13
60
44
9
76
69
69
10
8
55
39
n/a
71
64
64
Concentric Termination Elevation 4,501 - 10,000 ft
Number of 90° Elbows
Used
2" Pipe
2" Pipe
2" Pipe
Capacity
Capacity
Capacity
70
90
110
70
90
110
70
90
110
1
53
37
n/a
100
84
49
116
109
109
2
48
32
95
79
44
111
104
104
3
43
27
90
74
39
106
99
99
4
38
22
85
69
34
101
94
94
5
33
17
80
64
29
96
89
89
6
28
12
75
59
24
91
84
84
7
23
7
70
54
19
86
79
79
8
18
n/a
65
49
14
81
74
74
9
13
60
44
9
76
69
69
10
8
55
39
n/a
71
64
64
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
Table 5B.