Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4500 ft
Number of 90° Elbows
Used
2" Pipe
2" Pipe
2" Pipe
Capacity
Capacity
Capacity
70
90
110
70
90
110
70
90
110
1
61
39
19
110
88
53
132
113
113
2
56
34
14
105
83
48
127
108
108
3
51
29
9
100
78
43
122
103
103
4
46
24
n/a
95
73
38
117
98
98
5
41
19
90
68
33
112
93
93
6
36
14
85
63
28
107
88
88
7
31
9
80
58
23
102
83
83
8
26
n/a
75
53
18
97
78
78
9
21
70
48
13
92
73
73
10
16
65
43
8
87
68
68
Standard Termination Elevation 4500 - 10,000 ft
Number of 90° Elbows
Used
2" Pipe
2" Pipe
2" Pipe
Capacity
Capacity
Capacity
70
90
110
70
90
110
70
90
110
1
61
39
n/a
110
88
53
132
113
113
2
56
34
105
83
48
127
108
108
3
51
29
100
78
43
122
103
103
4
46
24
95
73
38
117
98
98
5
41
19
90
68
33
112
93
93
6
36
14
85
63
28
107
88
88
7
31
9
80
58
23
102
83
83
8
26
n/a
75
53
18
97
78
78
9
21
70
48
13
92
73
73
10
16
65
43
8
87
68
68
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
Table 5A.