ON
OFF
1
2
3
4
5
6
E.
Battery Operation
SYSTEM START / SHUT DOWN / RESET:
FUNCTION
OPERATION
Start
Press the RESET button for 3s when the battery is in sleep mode to
switch it on. Led on the panel flashes from the Left to Right.
Shut down
Press the RESET button for 3s when the battery is in idle/discharge
mode to switch it OFF. Led on the panel flashes from Right to Left.
Resetting
Press the RESET button for 6s when the battery is in idle/discharge
mode to reset the BMS.
COMMUNICATION PORTS:
COMPONENT
FUNCTION / DESCRIPTION
RS232 (RJ11)
Not active
CAN Ports (RJ45 x 2)
Serial communication via CAN
Bus. PIN configuration as follows:
-
7 : CAN-H
-
8 : CAN-L
RS485 Ports (RJ45 x 2)
Pin configuration as follows:
-
1/8 : A
-
2/7 : B
-
3/6 : GND
-
4/5 : NC
DIP SWITCH PANEL CONFIGURATION:
Address
DIP Switch Number
Master
/ Slave
(CAN)
Definition
(RS485)
Parallel Configuration
#1
#2
#3
#4
1
ON OFF OFF
OFF
Master
Pack1
2
OFF ON OFF
OFF
Slave 1
Pack2
3
ON ON OFF
OFF
Slave 2
Pack3
4
OFF OFF ON
OFF
Slave 3
Pack4
5
ON OFF ON
OFF
Slave 4
Pack5
6
OFF ON ON
OFF
Slave 5
Pack6
7
ON ON ON
OFF
Slave 6
Pack7
8
OFF OFF OFF
ON
Slave 7
Pack8
9
ON OFF OFF
ON
Slave 8
Pack9
It is essential to set the DIP address number in order when connected with a CAN bus inverter,
otherwise the BMS will report an error.