background image

ON

 

OFF

 

1

 

2

 

3

 

4

 

5

 

6

 

E.

 

Battery Operation 

 

SYSTEM START / SHUT DOWN / RESET: 
 

FUNCTION 

OPERATION 

Start 

Press the RESET button for 3s when the battery is in sleep mode to 
switch it on. Led on the panel flashes from the Left to Right. 

Shut down 

Press the RESET button for 3s when the battery is in idle/discharge 
mode to switch it OFF. Led on the panel flashes from Right to Left. 

Resetting 

Press the RESET button for 6s when the battery is in idle/discharge 
mode to reset the BMS. 

 

 

 

COMMUNICATION PORTS: 

 

COMPONENT 

FUNCTION / DESCRIPTION 

RS232 (RJ11) 

Not active 

CAN Ports (RJ45 x 2) 

Serial communication via CAN 
Bus. PIN configuration as follows: 

-

 

7 : CAN-H 

-

 

8 : CAN-L 

 

   

 

 

RS485 Ports (RJ45 x 2) 

Pin configuration as follows: 

-

 

1/8 : A 

-

 

2/7 : B 

-

 

3/6 : GND 

-

 

4/5 : NC 
 

 
 

DIP SWITCH PANEL CONFIGURATION: 

 

Address 

DIP Switch Number 

Master 

/ Slave 

(CAN) 

Definition 

(RS485) 

Parallel Configuration 

 

#1

 

#2

 

#3

 

#4

 

 

 

ON  OFF  OFF 

OFF 

Master 

Pack1 

OFF  ON  OFF 

OFF 

Slave 1 

Pack2 

ON  ON  OFF 

OFF 

Slave 2 

Pack3 

OFF  OFF  ON 

OFF 

Slave 3 

Pack4 

ON  OFF  ON 

OFF 

Slave 4 

Pack5 

OFF  ON  ON 

OFF 

Slave 5 

Pack6 

ON  ON  ON 

OFF 

Slave 6 

Pack7 

OFF  OFF  OFF 

ON 

Slave 7 

Pack8 

ON  OFF  OFF 

ON 

Slave 8 

Pack9 

 

It is essential to set the DIP address number in order when connected with a CAN bus inverter, 
otherwise the BMS will report an error. 

 

Summary of Contents for CPS 5000-King

Page 1: ...Installation Manual CPS 5000 Vic 5 2k...

Page 2: ...EMENTS C STRUCTURAL INFORMATION 1 LIST OF COMPONENTS 2 PRODUCT LAYOUT D INSTALLATION 1 PRE INSTALLATION 1 1 Product Applications 1 2 Requirements Limitations 1 3 Wiring Diagram 2 STANDARD INSTALLATION...

Page 3: ...V 100 5 2k DU Daily Use Lithium Iron Phosphate battery See G Supporting Documents for more technical information Battery Pack term Two or more BN52V 100 5 2k DU batteries connected to each other in pa...

Page 4: ...importance that any all requirements listed below are strictly adhered to Product installation maintenance should be performed by a qualified electrical installer or authorised BlueNova representative...

Page 5: ...have to be obtained following completion of such installations as per South African legislature CoC documents issued in this regard should be kept safe will be supportive in the event of future warra...

Page 6: ...The distribution boards in the top section contain the following components The diagram below illustrates the layout of the unit s BN52V 100 5 2k DU battery...

Page 7: ...at the product integrated inverter is compatible by design with several peripheral hardware components A few applications for which the product can be configured are described below Product Applicatio...

Page 8: ...figured for such purposes Please see D3 Adding Solar below Familiarising yourself with system subcomponents minimises the risk of failure during product installation For non standard applications of t...

Page 9: ...l the rawl bolts supplied The top section should be mounted as high as possible without compromising access to the inverter s user interface and or legibility of any information that might be displaye...

Page 10: ...verter will auto disconnect At temperatures higher than 25 C maximum inverter output will derate to less than 4000W See the inverter manual included with shipment for more information The AC breakers...

Page 11: ...4 ADDING MORE BATTERIES Additional batteries can be connected to the original battery to increase overall capacity Batteries should be connected as illustrated below...

Page 12: ...32 RJ11 Not active CAN Ports RJ45 x 2 Serial communication via CAN Bus PIN configuration as follows 7 CAN H 8 CAN L RS485 Ports RJ45 x 2 Pin configuration as follows 1 8 A 2 7 B 3 6 GND 4 5 NC DIP SWI...

Page 13: ...me capacity on Flash 3 Highest LED Flash 2 OV Protect on on on on on off OC Protect charge limit off off off off off off on Stop charging Charge limit According to real time capacity on off Highest LE...

Page 14: ...ry display If the batteries are not charged repeat steps 1 to 3 above Should the system not start up at this point please contact BlueNova technical support G Emergency First Aid 1 IN CASE OF FIRE a E...

Reviews: