9.2. - MODBUS © protocol
Modbus RTU Frame Format:
Address code
1 BYTE
Slave device address
1-247
Function code
1 BYTE
Indicates the function codes
like read coils / inputs
Data code
N BYTE
Starting address, high byte
Starting address, low byte
Number of registers, high byte
Number of registers, low byte
Error Check code
2 BYTE
Cyclical Redundancy Check (
CRC )
MODBUS FUNCTIONS
Code:
Meaning:
Description:
FUNCTION 03/04
Reading of n Words
This function permits to read all
the electrical parameters of the
BJ194…series.
FUNCTION 08
Clear energy counters
Cleared energy data by the PC
(*User also can clear energy
counter on meter operation,
refer the
User Manual
related
section)
FUNCTION 16
Preset Multiple Registers
Write value in to the relevant
register