then press
again, enter the level 3 menu.
Use
and
to input the new password:
Note:
Please do not change the password, If necessary, please contact Blue Jay technical !!
7.6. – Menu Structure
level 1
Level 2
Level 3
Description
(LCD backlight time)
LCd.t
0000~1000
Factory default is 0005
(Clear energy
counters)
CLr.E
Unrecoverable for Clear data
(Display mode)
dISP
Manual or
Automatic
Factory default is manual
(System setting)
SYS
(Change the password)
CodE
0000~9999
Default is 0001
(Net)
Lin.e
N.3.4, N.3.3, N.1
Select the input signal network
measurement
(Voltage Range)
U.SCL
100V, 220V,
380V
Select the range of measured
voltage signal
(Current Range)
I.SCL
5A and 1A
Select the range of measured
current signal
(Voltage transformation
ratio)
R.PT
1-9999
Setting voltage signal
transformation ratio = 1 / 2 scale
(Signal input)
-
IN-
(Current transformation
ratio)
R.CT
1-9999
Setting current signal
transformation ratio = 1 / 2 scale
(Address)
ADDR
1-247
Instrument address range 1-247
(Communication
speed)
BAUD
4800~9600
Default is 4800
(Communication
Parameters)
bUS
Protocol
DATA
o.8.1; e.8.1;
n.8.1
Factory default communication
mode for the word (
n.8.1
)
(Output type)
TYPE
r.n, Alr, OFF
Default is
Alr
(Set output delay)
DELY
0000~9999
Default is 0010
Choose the electrical
parameter
PArA
I3-H, PS-H...U3-
H
Default is I3-H
(Set the alarm value)
VALU
0000~9999
Default is 0050
(Digital output
setting)
DO-1
hysteresis value
HYS
4800~9600
Default is 4800