r.n:
Mean remote control mode, there have pulse and level output mode, more detail refer
chapter
7.4.2
.
Host inquiry:
01
05
00 01
FF 00
DD FA
Address
Code
Relay address
Relay value
(FF00:close; 0000: open)
CRC
Slave answer
01
05
00 01
FF 00
DD FA
Address
Code
Relay address
Relay value
(FF00:close; 0000: open)
CRC
RS485 communication please refer to chapter
9.1
ALr:
Mean directly alarm mode
OFF:
Mean the relay will not work
7.4.2. -
Set output delay
In level 1 menu of “DO-1”.
Choose item “DELY”, and the meter shows like this:
Then press
, enter the level 3 menu, user can set the delay value:
Press
to input the number, from “0~9”. Press
to move the cursor. After
password switch press
to confirm the input, value is 1~9999.
(Default 0010)
Note:
The setting of relay value is indicating the width pulse output; value “0000” is for level
output. The setting value resolution is 100ms, which means “0001” is 100ms, “9999”
means 999.9s.
0 for level output, 1~9999 for pulse output