12
Charge on.
Figure 3-5. Wiring
3-4. Please
use following wire and torque force when connecting to input terminal block. using conductor
type other than RHH, RHW and RHW-2 with outer covering.
Model
Terminal Conductor Screw Rating
Torque - lb-in (N-m)
IQW2-80U-M1-R2-N-25 (Ad-
vanced) IQW2-80U-W1-N1-
N-25 (Smart) IQW2-32U-M1-R2-
N-25 (32A)
L1, L2
2 AWG
M8
90C, copper wire 97.4 (11)
G
8 AWG
M6
60C, copper wire 70.8 (8)
IQW2-00U-M1-R2-N-00 (Kiosk)
L1, L2,
G
14 AWG
M4
60C, copper wire 7.1 (0.8)
CAUTION: “To reduce the risk of the fire, connect only to a circuit provided with (@) amperes maximum
branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70, and
the Canadian Electrical Code, Part I, C22.2”.
Model
Current Rating
IQW2-80U-M1-R2-N-25 (Advanced)
IQW2-80U-W1-N1-N-25 (Smart)
100 A
IQW2-32U-M1-R2-N-25 (32A)
40 A
IQW2-00U-M1-R2-N-00 (Kiosk)
15 A