1-800-486-4328
1-204-633-1999
100 Eagle Drive
Winnipeg, MB Canada
www.hermannelson.com
SETTING GAS FIRING RATES
1.) Choose BTU required and fuel supplied. For example 399,000 BTU and Natural Gas with the Beckett CG10-24.
2.) Adjust the manifold pressure to the recommended setting (5).
3.) Check nameplate for recommended air setting. A 10/0 air setting is recommended.
4.) Measure the carbon monoxide level and adjust air settings, if necessary, to regulate it to about 50 PPM for a
starting point.
5.) Measure the O2 or CO2 at the 50 PPM level. For example, assume the O2 is 1.5% (11% CO2).
6.) Open the air adjustment until the O2 level is increased to 3% O2. This should reduce the CO level and provide a
margin of reserve air to accommodate variable conditions.
7.) Sample the CO level again. It should be in the 0 to 50 PPM range—50 according to settings.
8.) Check the draft to ensure it still meets specifications. If a major change in draft is required, repeat the above
steps.
9.) Perform any final adjustments and lock the air settings securely. Run the burner through several cycles to verify
prompt ignition and stable burner operation.
SETTING OIL FIRING RATES
1.) Choose BTU required. For example 396,000 BTU with the Beckett CF375 oil burner.
2.) Check name plate for recommended pump pressure. 200 psi is recommended.
3.) Check nameplate for recommended air setting. A 5/3 air setting is recommended.
4.) Look at pressure gauge in pump gauge port and start the burner. Operate for 5 minutes until blower fan starts.
5.) Adjust pump pressure to 200 PSI.
6.) Adjust air band to 3 and adjust air shutter to 5.
7.) Check smoke and CO2 levels. Once attained, lock air band and shutter in place.
8.) Shut off burner, let unit cool down. The unit is now adjusted for 396,000 input BTU’s.
THERMOSTAT OPERATION
The BLAZE 400 D/G can be operated with a thermostat control.
An optional remote thermostat is available for temperature control for the space being heated. To connect the
heatstat, simply plug the heatstat into an extension cord and the extension cord into the outlet marked “REMOTE
STAT”. Make sure selector is in the “STAT ON” position. Place the remote thermostat into the space that is being
heated. The unit will now shut down at the remote thermostat temperature setting.
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 |
www.campoequipment.com
P a g e
|