INSTALLATION INSTRUCTIONS
1.) The recommendations of local authorities having jurisdiction must be followed. For
recommended installation practices refer to C.S.A. standard B139. (CANADA)
2.) When firing the unit in an enclosed area allow 1 square inch per thousand BTU’s (refer to
C.S.A. B139) to allow the free entry of the air required for operation.
3.) For electrical supply: 120V
INSTALLATION
12/3 AWG UPTO 50FT
10/3 AWG BEYOND 50FT
Do not operate the unit in partly ventilated areas without a flue pipe or in close proximity to
combustible surfaces or materials. Non Combustible floor must extend 6 feet on all sides of
the unit.
NOTE: Installation clearances are as follows:
TOP
3 feet
SIDES
3 feet
BURNER END
3 feet
DISCHARGE END
10 feet
VENT CONNECTOR
3 feet
COMBUSTIBLE FLOOR
6 feet
FLUE PIPE CONNECTIONS
VENT TO OUTDOORS
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY
When the heater is connected to a flue pipe the flue pipe shall terminate in a vertical section at
least two feet long. Horizontal runs should have rise ratio of 1 in 10 away from the heater.
Where
down drafts are liable to occur a vent cap should be used. All venting should correspond with the
CSA B139 standard or local codes
.
CAUTION: HEATER FLUE TEMPERATURES CAN REACH 700 °F TO 900 °F THEREFORE IT IS
A RANGE THAT IS BOTH HAZARDOUS TO HUMANS AND HIGHER THAN THE AUTO-
IGNITION TEMPERATURES OF MANY MATERIALS. THEREFORE EXERCISE CAUTION IN
HEATER PLACEMENT AND THE USE OF AN INSULATED GUARD AND STACK IS HIGHLY
RECOMMENDED
.
Horizontal venting runs shall always terminate with a minimum 24” vertical.
NOTE: FOR OPTIMAL COMBUSTION PERFORMANCE A 30” C-VENT FLUE EXTENSION WITH
RAIN CAP IS RECOMMENDED AT ALL TIMES.
Recommended chimney draft - .05 inches of water column