KOMFORT EC DE
Function
Indication
12 Standby Mode Settings
Select the
STANDBY MODE
item in the
Engineering menu
and press
ENTER
.
Use
or
to select 0 or 1 in
AIR FLOW
window:
•
0
- for deactivation of the unit.
•
1
- for activation of the Standby mode. In the
Standby mode
the unit
operates at the first speed at temperature set by
or
buttons
in
TEMPERATURE
window.
Press
ENTER
.
To return to
Engineering menu
without saving changes press
EXIT
.
13 Display brightness adjustment
Select the
BRIGHTNESS ADJUSTMENT
item in the
Engineering menu
and press
ENTER
.
Use
or
to set brightness for the operation conditions and
sleep mode. The control panel changes into the sleep mode 30 seconds
after the last pressing.
Press
ENTER
.
To return to
Engineering menu
without saving changes press
EXIT
.
14 Humidity setting
Select the
HUMIDITY SETTING
item in the
Engineering menu
and press
ENTER
.
Select the humidity sensor type for humidity control:
•
DUCT
(duct humidity sensor is a specially ordered accessory
and is not included into the basic complete set);
•
ROOM
humidity sensor
.
Set the required humidity point using
or
.
Press
ENTER
.
To return to
Engineering menu
without saving changes press
EXIT
.
In the humidity control mode the minimum air flow matches the air flow
at the first speed.
15 Error control
Select the
ERROR CONTROL
item and press
ENTER
to review the
last registered error.
The display shows the error date and code.
Press
EXIT
to return to the
Engineering menu
.
The error list is stated in the table 7.
Table 6. Operation and parameter setup of the unit (continued)