www.blaubergventilatoren.de
13
KOMFORT EC DE
For the control panel wiring diagram refer to fig. 15. The room temperature
sensor is integrated into the control panel, for that reason the control panel
must be installed in a temperature balanced place, at least 1 m away from the
heating equipment, doors and windows.
Fix the control panel to the wall using the screws and connect it to
the air handling unit using a supplied four-wire connecting cable. The
recommended cross section of the connecting cable is shown in table 5. The
recommended minimum control panel voltage is 11 V.
The control panel is supplied assembled and pre-wired to the unit. In
case of need to re-assemble the control panel please follow the assembly
order shown in fig. 15.
Recommended cable length from
the wall surface is 90 mm
1
3
2
5
6
4
Fig. 15. Control panel mounting
WARNING
Do not lay the cable in close proximity parallel to the cable from the control panel! Do not coil the cable from the control panel in
loops while laying it.
!
Table 5. Recommended cross section of the connecting cable between the control panel and the air handling unit
Parameter
Value
Cable cross section
≥ 0,12 mm²
≥ 0,25 mm²
Cable length
up to 15 m
up to 50 m
KOMFORT_EC_DE v1(1)_EN.indd 13