12
www.blaubergventilatoren.de
KOMFORT EC DE
1
3
2
4
130
86
30
The FS1 duct humidity sensor is a specially ordered accessory. Connect
the contact socket of the humidity sensor to the contact socket located
inside of the heat recovery unit.
After that fix the sensor using the clamp and the holder in the air duct
upstream of the heat exchanger.
1.
2.
3.
The unit is supplied with an outdoor temperature sensor.
The outdoor temperature sensor mounting is as follows, fig. 13:
1. Remove two screws that retain the sensor cover.
2. Take off the sensor cover.
3. Install the sensor on the outer wall. The installation place must not be
subjected to direct solar light.
4. Install the sensor cover back.
5. Connect the sensor to the X1 terminal block in compliance with the
electric wiring diagram, fig. 9 and fig. 11.
OUTER TEMPERATURE SENSOR MOUNTING AND CONNECTION
HUMIDITY E SENSOR MOUNTING AND CONNECTION
Fig. 13. Outdoor temperature sensor mounting
Fig. 14. Control panel overall dimensions
CONTROL PANEL MOUNTING
The units have integrated control system with a wall-mounted control
panel and a sensor display. The standard delivery set includes a 10 m cable
for connection of the unit and the control panel. The control panel technical
data are shown in table 4.
Table 4. Control panel technical data
Parameter
Value
Ambient temperature [°C]
+5 up to +40
Relative humidity [%]
5 up to 80
(no condensation)
Cable cross section [mm
2
]
0.25 up to 0.35
Material
plastic
Cable length [m]
up to 15
Ingress protection rating
IP20
KOMFORT_EC_DE v1(1)_EN.indd 12
07.08.2015 12:39:59