POSSIBLE REASONS AND TROUBLESHOOTING

Problem

Possible reasons

Troubleshooting

The fan does not get started. No power supply.

Check the automatic circuit breaker. Check the 
electric connections.

Jammed motor.

Carefully check the fan impeller for possible seizure 
and eliminate it, if necessary. If the impeller is in 
order, replace the electric motor.

The automatic breaker 
activates upon fan start-up.

Short circuit in the fan or the electric circuit 
between the fan and the automatic circuit 
breaker.

Eliminate the cause of a short circuit.

Excessive current consumption due to an 
overload in the electric mains.

Eliminate the cause of excessive current 
consumption.

Improper fan starting method.

Use a soft starter or frequency converter to start the 
motor (see “Asynchronous electric motor starting 
methods” in the “Connection to power mains” 
section).

Improper automatic circuit breaker.

Re-select the automatic circuit breaker in 
accordance with the current regulations and 
equipment specifications.

The installed automatic circuit breaker is of poor 
quality or its actual performance falls short of 
the rated values stated by the manufacturer.

Re-select the automatic circuit breaker by choosing 
a unit which successfully passed commutation 
and load tests and has a technical compliance 
certificate.
The selection should be limited to the top five 
foreign switching equipment manufacturers.

The fan fails to reach the 
required rotation speed due 
to serious overheating of the 
fan motor.

Fan motor overloaded.

Eliminate the overload.

Improper fan starting method.

Use a soft starter or frequency converter to start the 
motor (see “Asynchronous electric motor starting 
methods” in the “Connection to power mains” 
section).

The fan motor runs at 
overload capacity with 
current consumption in 
excess of the rated value.

Wrong motor phasing. The impeller rotates in 
the opposite direction of the arrow on the fan 
casing.

If necessary, change the impeller rotation direction 
by changing the phase sequence on the electric 
motor terminals.

The fan supplies more air 
than expected.

Wrong choice of the fan.

Replace the fan with a unit of proper standard size.

centro-Jet

14

www.blaubergventilatoren.de

Summary of Contents for Centro-Jet Series

Page 1: ...Impulse centrifugal fan USER S MANUAL EN Centro Jet...

Page 2: ...Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this pub...

Page 3: ...g the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation ope...

Page 4: ...the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or em...

Page 5: ...n of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogenic germs THE UN...

Page 6: ...F H L K Centro Jet 50N 290 1355 935 1005 1065 90 180 350 96 Centro Jet 85N 330 1605 1105 1175 1235 110 230 390 136 Centro Jet 100N 330 1605 1105 1175 1235 110 230 390 138 TECHNICAL DATA Centro Jet X...

Page 7: ...5 55 C 55 C Centro Jet 85N 4 200 2 200 C 2 hours F200 Centro Jet 85N 4 300 2 300 C 2 hours F300 Centro Jet 85N 4 400 2 400 C 2 hours F400 85N double speed Centro Jet 85N 4 6 3 400 50 9750 5950 2 2 0 7...

Page 8: ...motor or a double speed 4 6 or 4 8 pole asynchronous motor Steel impeller with backward curved blades Before installing the unit carry out the following checks Make sure that the fan impeller rotates...

Page 9: ...tion method i e overhead in pipes or inside the walls Connection of the fan for smoke extraction must be performed via a cable with a respective fire resistance class Quality and mounting of the fire...

Page 10: ...Centro Jet 50N 4 Centro Jet 85N 4 Centro Jet 100N 4 X1 L3 L1 L2 U1 W1 V1 U2 W2 V2 PE L2 L3 L1 1 2 3 4 5 6 400 V 50 Hz 400 V 60 Hz Double speed Centro Jet 50N 4 6 Centro Jet 85N 4 6 Centro Jet 100N 4...

Page 11: ...SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals limit the motor curren...

Page 12: ...circuit breakers contactors and motor starters is not designed to withstand prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of ti...

Page 13: ...hub for proper tightness and tighten it up if necessary Check the bolt connecting the motor shaft to the hub for proper tightness and tighten it up if necessary Technical maintenance must be carried...

Page 14: ...ons The installed automatic circuit breaker is of poor quality or its actual performance falls short of the rated values stated by the manufacturer Re select the automatic circuit breaker by choosing...

Page 15: ...objects or debris Clean the impeller from foreign objects or debris Increased noise vibration in the fan Loose screw connections Check the screw connections for proper tightness No vibration mounts o...

Page 16: ...andling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechani...

Page 17: ...nation of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit componen...

Page 18: ...Centro Jet 18 www blaubergventilatoren de...

Page 19: ...___ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signat...

Page 20: ...www blaubergventilatoren de B117EN 03...

Reviews: