ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS

There are several methods for starting asynchronous squirrel-cage electric motors.
The most common methods are: direct-on-line (DOL), with a soft starter (SS) or with a frequency converter (FC).

Direct-on-line starting

In case of direct-on-line starting (i.e. by connecting the motor to the electric mains with a simple line contactor), the motor starting 
time significantly increases due to high inertia of the impeller, which, in turn, results in high in-rush starting currents in the circuit. These 
currents of long duration may cause voltage slumps (especially if the feed line section falls short of the requirements), which may affect 
load operation.
The in-rush current consumed by an electric motor in case of DOL starting is 5-8 times larger than the rated value (or even 10-14 times 
larger in some rare instances). It should be noted that the torque developed by the motor also significantly exceeds the rated value.
Upon energisation the motor operates as a transformer with a squirrel-cage secondary winding formed by the rotor cage with a very low 
resistance.
The rotor develops high induced current causing a rush of current in the feed line.
The startup torque during starting averages 0.5-1.5 of the rated torque value.

Despite such advantages as simple construction, high startup current, quick start and low cost, direct-on-line systems are suitable only 
in the following cases:
•  the motor power is low compared to the mains power which limits the adverse effect of the rush of current
•  the driven mechanism does not require gradual speed build-up or is equipped with a damping device to smooth out the inrush
•  the high startup torque has no adverse effects on the operation of the driven mechanism

Soft start. SS starting.

A soft starter gradually increases the voltage supplied to the motor – from the initial to the rated value.
This starting system can be used to meet the following goals:
•  limit the motor current
•  regulate the torque

Regulation by limiting the current sets the maximum in-rush current equal to 300-400 % (or  250 % in some rare instances) of the rated 
current and reduces torque characteristics. This type of regulation is especially suited for turbomachinery such as centrifugal pumps and 
fans.
Regulation by variation of torque optimizes the torque during startup and reduces in-rush current in the circuit. These conditions are 
suitable for mechanisms with constant load resistance.
This type of soft starting may differ in the implementation pattern:
•  motor start
•  motor start and stop
•  device bridging at the end of start sequence
•  start and stop of several motors in stage circuits

Soft start. FC starting.

During the starting the FC raises the frequency from 0 Hz to the electrical mains frequency (50 or 60 Hz). As the frequency is increased 
gradually, the motor can be assumed to operate at its rated speed for a given frequency value. Furthermore, on the assumption that the 
motor runs at its rated speed the nominal torque should be immediately available whereas the current will be approximately equal to 
the rated value.
This starting system is used for speed control and regulation and can be used in the following cases:
•  start with high-inertia load
•  start with high load and limited-capacity power supply source
•  optimization of electric power consumption depending on turbomachinery speed
The aforementioned starting system can be used for all types of mechanisms.

Problems associated with DOL starting

The problems caused by DOL starting may be divided into two groups:
1.  An abrupt start causes mechanical shock, jolts in the mechanism, shock removal of free play etc.
2.  A heavy start cannot be completed.

www.blaubergventilatoren.de

centro-Jet

11

Summary of Contents for Centro-Jet Series

Page 1: ...Impulse centrifugal fan USER S MANUAL EN Centro Jet...

Page 2: ...Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this pub...

Page 3: ...g the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation ope...

Page 4: ...the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or em...

Page 5: ...n of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogenic germs THE UN...

Page 6: ...F H L K Centro Jet 50N 290 1355 935 1005 1065 90 180 350 96 Centro Jet 85N 330 1605 1105 1175 1235 110 230 390 136 Centro Jet 100N 330 1605 1105 1175 1235 110 230 390 138 TECHNICAL DATA Centro Jet X...

Page 7: ...5 55 C 55 C Centro Jet 85N 4 200 2 200 C 2 hours F200 Centro Jet 85N 4 300 2 300 C 2 hours F300 Centro Jet 85N 4 400 2 400 C 2 hours F400 85N double speed Centro Jet 85N 4 6 3 400 50 9750 5950 2 2 0 7...

Page 8: ...motor or a double speed 4 6 or 4 8 pole asynchronous motor Steel impeller with backward curved blades Before installing the unit carry out the following checks Make sure that the fan impeller rotates...

Page 9: ...tion method i e overhead in pipes or inside the walls Connection of the fan for smoke extraction must be performed via a cable with a respective fire resistance class Quality and mounting of the fire...

Page 10: ...Centro Jet 50N 4 Centro Jet 85N 4 Centro Jet 100N 4 X1 L3 L1 L2 U1 W1 V1 U2 W2 V2 PE L2 L3 L1 1 2 3 4 5 6 400 V 50 Hz 400 V 60 Hz Double speed Centro Jet 50N 4 6 Centro Jet 85N 4 6 Centro Jet 100N 4...

Page 11: ...SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals limit the motor curren...

Page 12: ...circuit breakers contactors and motor starters is not designed to withstand prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of ti...

Page 13: ...hub for proper tightness and tighten it up if necessary Check the bolt connecting the motor shaft to the hub for proper tightness and tighten it up if necessary Technical maintenance must be carried...

Page 14: ...ons The installed automatic circuit breaker is of poor quality or its actual performance falls short of the rated values stated by the manufacturer Re select the automatic circuit breaker by choosing...

Page 15: ...objects or debris Clean the impeller from foreign objects or debris Increased noise vibration in the fan Loose screw connections Check the screw connections for proper tightness No vibration mounts o...

Page 16: ...andling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechani...

Page 17: ...nation of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit componen...

Page 18: ...Centro Jet 18 www blaubergventilatoren de...

Page 19: ...___ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signat...

Page 20: ...www blaubergventilatoren de B117EN 03...

Reviews: