background image

Let us review three variations of a heavy start:

1. The feed line performance is barely sufficient or insufficient to maintain the induced current.

Typical symptoms: 

Upon starting the circuit breakers at the system input are tripped; the lights, certain relays and contactors go off, 

and the supply generator shuts down.

Solution: 

In the best-case scenario an SS device may help reduce the in-rush current to 250 % of the motor rated current. If this is 

insufficient, an FC is necessary.

2. The motor cannot start the mechanism with DOL starting.

Typical symptoms: 

The motor fails to turn or “freezes” at certain speed which is maintained until actuation of the protection suite.

Solution: 

This problem may not be solved with an SS device. The motor develops insufficient shaft torque. However, this problem can 

be addressed by using an FC, but each case may be different.

3. The motor spins up the mechanism with authority, but fails to reach the rated rotation speed.

Typical symptoms: 

The input automatic circuit breaker is tripped during spin-up. This often happens with heavy-weight fans with a 

considerable rotation speed.

Solution: 

Such problems may be addressed with an SS device, but not with 100 % certainty. The closer the motor speed to the rated 

value during the actuation of the protective equipment, the higher the chances of success. The use of an FC in this case helps solve the 
problem fundamentally.

Standard switching equipment (automatic circuit breakers, contactors and motor starters) is not designed to withstand 

prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of 

time.

Using switching equipment with a higher maximum current rating renders the electric motor protection system less sensitive. 

As a result the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold.

Such problems as mentioned above can only be addressed by utilizing a soft starter or a frequency converter to start the fan.

COMMISSIONING

THE ORGANISATION RESPONSIBLE FOR THE COMMISSIONING SHALL BE RESPONSIBLE 

FOR PROPER MOTOR PHASING AND STARTING PATTERN SELECTION.

•  After fan starting make sure that the motor rotates properly without undue vibration and abnormal noise.
•  Make sure that the fan impeller rotates in the direction marked by the arrow on the fan casing. If necessary, change the impeller 

rotation direction by changing the phase sequence on the electric motor terminals.

•  Make sure that the fan energy consumption complies with the value given on the equipment nameplate and check the motor for 

overheating.

•  The phase current should be checked once the fan reaches the rated operating conditions.
•  Do not switch the fan on and off several times without pauses as this may result in damage to the winding or insulation due to 

overheating.

DURING STARTING THE IN-RUSH CURRENTS OF THE FAN MAY SEVERAL TIMES EXCEED 

THE RATED VALUES. 

SEE “ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS” IN THE “CONNECTION 

TO POWER MAINS” SECTION

centro-Jet

12

www.blaubergventilatoren.de

Summary of Contents for Centro-Jet Series

Page 1: ...Impulse centrifugal fan USER S MANUAL EN Centro Jet...

Page 2: ...Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this pub...

Page 3: ...g the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation ope...

Page 4: ...the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or em...

Page 5: ...n of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogenic germs THE UN...

Page 6: ...F H L K Centro Jet 50N 290 1355 935 1005 1065 90 180 350 96 Centro Jet 85N 330 1605 1105 1175 1235 110 230 390 136 Centro Jet 100N 330 1605 1105 1175 1235 110 230 390 138 TECHNICAL DATA Centro Jet X...

Page 7: ...5 55 C 55 C Centro Jet 85N 4 200 2 200 C 2 hours F200 Centro Jet 85N 4 300 2 300 C 2 hours F300 Centro Jet 85N 4 400 2 400 C 2 hours F400 85N double speed Centro Jet 85N 4 6 3 400 50 9750 5950 2 2 0 7...

Page 8: ...motor or a double speed 4 6 or 4 8 pole asynchronous motor Steel impeller with backward curved blades Before installing the unit carry out the following checks Make sure that the fan impeller rotates...

Page 9: ...tion method i e overhead in pipes or inside the walls Connection of the fan for smoke extraction must be performed via a cable with a respective fire resistance class Quality and mounting of the fire...

Page 10: ...Centro Jet 50N 4 Centro Jet 85N 4 Centro Jet 100N 4 X1 L3 L1 L2 U1 W1 V1 U2 W2 V2 PE L2 L3 L1 1 2 3 4 5 6 400 V 50 Hz 400 V 60 Hz Double speed Centro Jet 50N 4 6 Centro Jet 85N 4 6 Centro Jet 100N 4...

Page 11: ...SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals limit the motor curren...

Page 12: ...circuit breakers contactors and motor starters is not designed to withstand prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of ti...

Page 13: ...hub for proper tightness and tighten it up if necessary Check the bolt connecting the motor shaft to the hub for proper tightness and tighten it up if necessary Technical maintenance must be carried...

Page 14: ...ons The installed automatic circuit breaker is of poor quality or its actual performance falls short of the rated values stated by the manufacturer Re select the automatic circuit breaker by choosing...

Page 15: ...objects or debris Clean the impeller from foreign objects or debris Increased noise vibration in the fan Loose screw connections Check the screw connections for proper tightness No vibration mounts o...

Page 16: ...andling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechani...

Page 17: ...nation of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit componen...

Page 18: ...Centro Jet 18 www blaubergventilatoren de...

Page 19: ...___ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signat...

Page 20: ...www blaubergventilatoren de B117EN 03...

Reviews: