ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS

There are several methods for starting asynchronous squirrel-cage electric motors.
The most common methods are: direct-on-line (DOL), with a soft starter (SS) or with a frequency converter (FC).

Direct-on-line starting

In case of direct-on-line starting (i.e. by connecting the motor to the electric mains with a simple line contactor), the motor starting 
time significantly increases due to high inertia of the impeller, which, in turn, results in high in-rush starting currents in the circuit. These 
currents of long duration may cause voltage slumps (especially if the feed line section falls short of the requirements), which may affect 
load operation.
The in-rush current consumed by an electric motor in case of DOL starting is 5-8 times larger than the rated value (or even 10-14 times 
larger in some rare instances). It should be noted that the torque developed by the motor also significantly exceeds the rated value.
Upon energisation the motor operates as a transformer with a squirrel-cage secondary winding formed by the rotor cage with a very low 
resistance.
The rotor develops high induced current causing a rush of current in the feed line.
The startup torque during starting averages 0.5-1.5 of the rated torque value.

Despite such advantages as simple construction, high startup current, quick start and low cost, direct-on-line systems are suitable only 
in the following cases:
•  the motor power is low compared to the mains power which limits the adverse effect of the rush of current
•  the driven mechanism does not require gradual speed build-up or is equipped with a damping device to smooth out the inrush
•  the high startup torque has no adverse effects on the operation of the driven mechanism

Soft start. SS starting.

A soft starter gradually increases the voltage supplied to the motor – from the initial to the rated value.
This starting system can be used to meet the following goals:
•  limit the motor current
•  regulate the torque

Regulation by limiting the current sets the maximum in-rush current equal to 300-400 % (or  250 % in some rare instances) of the rated 
current and reduces torque characteristics. This type of regulation is especially suited for turbomachinery such as centrifugal pumps and 
fans.
Regulation by variation of torque optimizes the torque during startup and reduces in-rush current in the circuit. These conditions are 
suitable for mechanisms with constant load resistance.
This type of soft starting may differ in the implementation pattern:
•  motor start
•  motor start and stop
•  device bridging at the end of start sequence
•  start and stop of several motors in stage circuits

Soft start. FC starting.

During the starting the FC raises the frequency from 0 Hz to the electrical mains frequency (50 or 60 Hz). As the frequency is increased 
gradually, the motor can be assumed to operate at its rated speed for a given frequency value. Furthermore, on the assumption that the 
motor runs at its rated speed the nominal torque should be immediately available whereas the current will be approximately equal to 
the rated value.
This starting system is used for speed control and regulation and can be used in the following cases:
•  start with high-inertia load
•  start with high load and limited-capacity power supply source
•  optimization of electric power consumption depending on turbomachinery speed
The aforementioned starting system can be used for all types of mechanisms.

Problems associated with DOL starting

The problems caused by DOL starting may be divided into two groups:
1.  An abrupt start causes mechanical shock, jolts in the mechanism, shock removal of free play etc.
2.  A heavy start cannot be completed.

Let us review three variations of a heavy start:

1. The feed line performance is barely sufficient or insufficient to maintain the induced current.

Typical symptoms: 

Upon starting the circuit breakers at the system input are tripped; the lights, certain relays and contactors go off, 

and the supply generator shuts down.

Solution: 

In the best-case scenario an SS device may help reduce the in-rush current to 250 % of the motor rated current. If this is 

insufficient, an FC is necessary.

Summary of Contents for Box

Page 1: ...Duct rectangular fan USER S MANUAL EN Box Box I Box F Box FI ...

Page 2: ... practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country Safety requirements 3 Purpose 5 Delivery set 5 Designation key 5 Technical data 6 Mounting and set up 12 Connection to power mains 13 Technical maintenance 17 Troubleshooting 19 Storage an...

Page 3: ...noise Misuse of the unit and any unauthorised modifications are not allowed Do not expose the device to adverse atmospheric agents rain sun etc Transported air must not contain any dust or other solid impurities sticky substances or fibrous materials Do not use the unit in a hazardous or explosive environment containing spirits gasoline insecticides etc Do not close or block the intake or extract ...

Page 4: ...aged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a safety hazard Ensure that the appliance is switched off from the supply mains before removing the guard WARNING If there are any unusual oscillating movements immediately stop using the appliance and contact the manufacturer its service agent or suitably qualified persons The replaceme...

Page 5: ...with high requirements to the noise level and with limited space for mounting The unit is rated for continuous operation The unit is a component part and is not designed for stand alone operation Transported air must not contain any flammable or explosive mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the form...

Page 6: ...PX4 IPX4 IPX4 IPX4 IPX4 Electric motor IP rating IP44 IP44 IP44 IP44 IP54 IP54 IP54 IP54 Box Box I 60x30 4E 60x30 4D 60x35 4E Voltage V 1 220 240 3 400 1 220 240 Frequency Hz 50 60 50 60 50 60 Power W 220 310 230 235 470 700 Current A 0 9 1 38 0 52 0 53 2 37 3 15 Maximum air flow m3 h 2470 2510 2530 2630 2950 3515 RPM min 1 1400 1450 1360 1600 1370 1460 Sound pressure level at 3 m distance dBA 55 ...

Page 7: ...90 735 36 38 Box 60x35 4D 600 620 640 350 370 390 390 735 36 38 Model Dimensions mm Weight kg B B1 B2 H H1 H2 H3 L Box 100x50 4D 1000 1020 1040 500 520 540 720 1150 126 0 Model Dimensions mm Weight kg B B1 B2 B3 H H1 H2 H3 L Box I 40x20 2E 400 420 440 500 200 220 240 360 500 24 5 Box I 50x25 2E 500 520 540 600 250 270 290 410 640 27 6 Box I 50x30 4E 500 520 540 600 300 320 340 460 680 37 2 Box I 5...

Page 8: ...3 Current A 0 67 3 10 1 70 1 59 0 8 Maximum air flow m3 h 1490 2350 2350 1550 1620 RPM min 1 930 1230 1300 890 910 Sound pressure level at 3 m distance dBA 45 38 57 47 56 47 47 39 51 41 Transported air temperature С 20 60 25 70 20 50 20 70 20 60 Ingress protection rating of the unit IPX4 IPX4 IPX4 IPX4 IPX4 Electric motor IP rating IP54 IP54 IP54 IP54 IP54 Box F Box FI 60x30 4E 60x30 4D 60x30 6E 6...

Page 9: ... 70 25 40 Ingress protection rating of the unit IPX4 IPX4 IPX4 IPX4 Electric motor IP rating IP54 IP54 IP54 IP54 Box F Box FI 70x40 6D 80x50 4D 80x50 6D 80x50 8D Unit voltage V 50 60 Hz 3 400 3 400 3 400 3 400 Power W 1150 5850 2790 1377 Current A 2 3 9 35 5 18 3 40 Maximum air flow m3 h 4050 8120 7610 5620 RPM min 1 890 1140 830 710 Sound pressure level at 3 m distance dBA 58 49 67 61 59 53 58 49...

Page 10: ...20 640 300 320 340 375 680 35 Box F 60x30 4D 600 620 640 300 320 340 375 680 35 Box F 60x30 6E 600 620 640 300 320 340 375 680 35 Box F 60x30 6D 600 620 640 300 320 340 375 680 35 Box F 60x35 4E 600 620 640 350 370 390 425 735 49 5 Box F 60x35 4D 600 620 640 350 370 390 425 735 49 5 Box F 60x35 6E 600 620 640 350 370 390 425 735 49 5 Box F 60x35 6D 600 620 640 350 370 390 425 735 49 5 Box F 70x40 ...

Page 11: ...FI 60x30 4E 600 620 640 670 300 320 340 480 680 56 Box FI 60x30 4D 600 620 640 670 300 320 340 480 680 56 Box FI 60x30 6E 600 620 640 670 300 320 340 480 680 56 Box FI 60x30 6D 600 620 640 670 300 320 340 480 680 56 Box FI 60x35 4E 600 620 640 670 350 370 390 530 735 72 Box FI 60x35 4D 600 620 640 670 350 370 390 530 735 72 Box FI 60x35 6E 600 620 640 670 350 370 390 530 735 72 Box FI 60x35 6D 600...

Page 12: ...y that the arrow on the fan casing matches the air flow direction in the system The fan should always be installed on its own hangers so that it does not load the flexible connectors and the connected air ducts The most suitable mounting option is fixing the unit to the ceiling with anchors or suspending it on perforated metal plates Before mounting apply a self adhesive seal to the end surfaces o...

Page 13: ...e for reference only The actual conductor cross section selection must be based on its type the maximum permissible heating insulation length and installation method in the air pipes or inside walls The recommended type of circuit breakers is D or C but with replacement to D or to a higher rating in case of tripping because of frequent start ups The recommended circuit breaker rated current and co...

Page 14: ...x30 4D units with a three phase motor Wiring diagram for Box Box I 60x35 4D units with a three phase motor 400 V 50 60 Hz L N X1 1 2 3 N L QF PE 230 В 50 60 Гц 4 PE L2 L1 QF PE 400 В 50 60 Гц L2 L1 X1 2 4 1 3 L3 L3 L2 L1 QF PE L2 L1 X1 2 4 1 3 L3 L3 PE L2 L1 QF PE 400 В 50 60 Гц L2 L1 X1 2 4 1 3 L3 L3 5 4 TW1 TW2 TW1 TW2 L2 L1 QF PE 400 В 50 60 Гц L2 L1 X1 2 7 1 3 L3 L3 5 4 6 V1 U1 W1 W2 PE U2 V2 ...

Page 15: ...the delivery set The TW1 TW2 TK1 TK2 are the electrical leads of the normally closed contact of the motor overheating protection Connect the contact in series to power circuit of the magnetic starter coil KM1 that starts the motor after pressing the S1 button After the motor overheating the contact gets broken and switches the starter coil off to cut power off and stop the motor The QF circuit bre...

Page 16: ...motor current regulate the torque Regulation by limiting the current sets the maximum in rush current equal to 300 400 or 250 in some rare instances of the rated current and reduces torque characteristics This type of regulation is especially suited for turbomachinery such as centrifugal pumps and fans Regulation by variation of torque optimizes the torque during startup and reduces in rush curren...

Page 17: ...motor protection system less sensitive As a result the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold Such problems as mentioned above can only be addressed by utilizing a soft starter or a frequency converter to start the fan MAKE SURE THAT THE FAN IMPELLER ROTATES IN THE DIRECTION MARKED BY THE ARROW ON THE FAN CASING IF NECESSARY CH...

Page 18: ...www ventilation system com Box Box I Box F Box FI 18 1 3 4 5 6 2 ...

Page 19: ... handling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage The unit must be transported only in the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transportation at ...

Page 20: ...ntact the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s ...

Page 21: ...INSTALLATION CERTIFICATE The Box _____________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and st...

Page 22: ...www ventilation system com Box Box I Box F Box FI 22 ...

Page 23: ...www ventilation system com Box Box I Box F Box FI 23 ...

Page 24: ...www ventilation system com B07EN 04 ...

Reviews: