background image

Problems associated with DOL starting

The problems caused by DOL starting may be divided into two groups:
1.  An abrupt start causes mechanical shock, jolts in the mechanism, shock removal of free play etc.
2.  A heavy start cannot be completed.

Let us review three variations of a heavy start:

1. The feed line performance is barely sufficient or insufficient to maintain the induced current.

Typical symptoms: 

Upon starting the circuit breakers at the system input are tripped; the lights, certain relays and contactors go off, 

and the supply generator shuts down.

Solution: 

In the best-case scenario an SS device may help reduce the in-rush current to 250 % of the motor rated current. If this is 

insufficient, an FC is necessary.

2. The motor cannot start the mechanism with DOL starting.

Typical symptoms: 

The motor fails to turn or “freezes” at certain speed which is maintained until actuation of the protection suite.

Solution: 

This problem may not be solved with an SS device. The motor develops insufficient shaft torque. However, this problem can 

be addressed by using an FC, but each case may be different.

3. The motor spins up the mechanism with authority, but fails to reach the rated rotation speed.

Typical symptoms: 

The input automatic circuit breaker is tripped during spin-up. This often happens with heavy-weight fans with a 

considerable rotation speed.

Solution: 

Such problems may be addressed with an SS device, but not with 100 % certainty. The closer the motor speed to the rated 

value during the actuation of the protective equipment, the higher the chances of success. The use of an FC in this case helps solve the 
problem fundamentally.

Standard switching equipment (automatic circuit breakers, contactors and motor starters) is not designed to withstand 

prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of 

time.

Using switching equipment with a higher maximum current rating renders the electric motor protection system less sensitive. 

As a result the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold.

Such problems as mentioned above can only be addressed by utilizing a soft starter or a frequency converter to start the fan.

COMMISSIONING

THE ORGANISATION RESPONSIBLE FOR THE COMMISSIONING SHALL BE RESPONSIBLE 

FOR PROPER MOTOR PHASING AND STARTING PATTERN SELECTION.

•  After fan starting make sure that the motor rotates properly without undue vibration and abnormal noise.
•  Make sure that the fan impeller rotates in the direction marked by the arrow on the fan casing. If necessary, change the impeller 

rotation direction by changing the phase sequence on the electric motor terminals.

•  Make sure that the fan energy consumption complies with the value given on the equipment nameplate and check the motor for 

overheating.

•  The phase current should be checked once the fan reaches the rated operating conditions.
•  Do not switch the fan on and off several times without pauses as this may result in damage to the winding or insulation due to 

overheating.

DURING STARTING THE IN-RUSH CURRENTS OF THE FAN MAY SEVERAL TIMES ExCEED 

THE RATED VALUES. 

SEE “ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS” IN THE “CONNECTION 

TO POWER MAINS” SECTION

www.blaubergventilatoren.de

Axis-p

13

Summary of Contents for AXIS-P Series

Page 1: ...Axial pressurisation fan USER S MANUAL EN Axis P...

Page 2: ...ny reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this publicat...

Page 3: ...ing the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation o...

Page 4: ...power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disc...

Page 5: ...stems with high air flow rates THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INST...

Page 6: ...60 40 C T tropical climate 10 50 C M maritime moderately cold climate 40 40 C O general climatic modification except maritime climate 60 50 C OM general maritime climatic modification 40 40 C V unive...

Page 7: ...al box Casing modification with a terminal box d n holes d n holes MODEL DIMENSIONS MM L D D1 D2 d n B Axis P400 350 450 400 450 490 8 12 480 Axis P450 350 450 550 450 500 540 8 12 525 Axis P500 350 4...

Page 8: ...quare cage rotor installed inside the casing The fan casing modifications depend on the electrical cable connection options The cable is connected to the electric motor terminal box via a cable gland...

Page 9: ...The length of the straight duct section downstream of the fan must be 1 5 2 D Installation of shorter air ducts may result in insufficient air pressure and air flow The flexible joints EVAF AF are re...

Page 10: ...crement Installation of a downstream contractor is not recommended Installation near bends To install the fan directly downstream of a bend elbow use a curved section with a large bending radius or an...

Page 11: ...on The fan must be integrated into a ventilation or smoke extraction system with an automatic control system The fan motor is rated for connection to 400 V 50 60 Hz three phase alternating current Con...

Page 12: ...smooth out the inrush the high startup torque has no adverse effects on the operation of the driven mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the moto...

Page 13: ...ces of success The use of an FC in this case helps solve the problem fundamentally Standard switching equipment automatic circuit breakers contactors and motor starters is not designed to withstand pr...

Page 14: ...rt No power supply Check the mains switch Check the electrical connections against the wiring diagram Jammed motor Carefully check the fan impeller for possible seizure and eliminate it if necessary I...

Page 15: ...place the fan with a unit of proper standard size The fan supplies less air than expected Wrong calculation of the ventilation network and wrong selection of the fan Re calculate the network parameter...

Page 16: ...handling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mecha...

Page 17: ...nded use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component The warranty...

Page 18: ...www blaubergventilatoren de Axis P 18...

Page 19: ...______ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Sig...

Page 20: ...www blaubergventilatoren de B118EN 05...

Reviews: